Check Method
Set T/H sensor alarm thresholds.
----End

5.7.5.2 Commissioning a T/H Sensor (BOM number:02310NBS)

If a T/H sensor is installed, perform the following steps to configure it.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1 to 6 of the DIP switch specify the device address in binary mode. ON
indicates 1, and OFF indicates 0.
Table 5-35 Setting a device address
Address
1
2
3
4
Step 2 Add a T/H sensor.
1.
2.
Table 5-36 Adding a T/H sensor
Path
System
Issue 02 (2019-02-28)
Toggle
Switch 1
ON
OFF
ON
OFF
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device type
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Parameters, and set High
temperature alarm threshold, Low temperature
alarm threshold, High humidity alarm threshold,
and Low humidity alarm threshold as required.
NOTE
The default values of High temperature alarm threshold,
Low temperature alarm threshold, High humidity alarm
threshold, and Low humidity alarm threshold are 30.0° C,
5.0° C, 85.0% RH, and 15.0% RH, respectively.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
Setting
Select T/H Sensor from the drop-down list box.
5 Power-On Commissioning
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Toggle
Switch 6
OFF
OFF
OFF
OFF