Setting And Adding A Pdu2000-M(C) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

5.3.11 Setting and Adding a PDU2000-M(C)

Procedure
Step 1 Set the PDU2000-M(C) monitoring parameters.
1.
2.
3.
4.
Step 2 Add a PDU2000-M(C).
1.
2.
Table 5-8 Adding a PDU2000-M(C)
Path
Issue 02 (2019-02-28)
After the PDU2000-M(C) is powered on, the LCM displays the initialization screen.
Figure 5-4 PDU2000-M(C) initialization screen
Press MENU to enter the device communications address screen.
Figure 5-5 PDU2000-M(C) communications settings
Set the PDU2000-M(C) address to 1 (ranging from 1 to 41) by pressing DOWN and UP.
Press MENU to confirm the settings.
The parameter settings take effect only if you press MENU and then the PDU2000-M(C) buzzes and
restarts. If you do not press MENU, the PDU2000-M(C) buzzes and restarts automatically after 30s and
the setting parameters are not saved.
Log in to the ECC800 WebUI as an administrator.
Add a PDU2000-M(C).
Parameter
Name
Copyright © Huawei Technologies Co., Ltd.
Setting
5 Power-On Commissioning
104

Hide quick links:

Advertisement