Commissioning A Smoke Sensor; Commissioning A Water Sensor - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

5.9.2 Commissioning a Smoke Sensor

If a smoke sensor is installed, perform the following steps to configure it.
Procedure
Step 1 Set smoke sensor parameters.
Step 2 Check the monitoring functions of smoke sensor.
Table 5-25 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
Step 3 (Optional) Set audible and visual alarm linkage function for the smoke sensor based on
requirements. You can follow the instructions in linking alarms with alarm beacon.
----End

5.9.3 Commissioning a Water Sensor

If a water sensor is installed, perform the following steps to configure it.
Issue 06 (2020-01-02)
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
Scenario 1: Connect the smoke sensor to the AI/DI port on the ECC800 (AI/DI_1 is used
as an example).
On the WebUI, choose Monitoring > System > ECC800 > Running Parameters >
AI/DI_1 Port Settings, set AI/DI_1 sensor to Enable, and click Submit. Set AI/DI_1
sensor name to Smoke sensor, check that AI/DI_1 sensor type is set to Smoke Sensor
or Smoke Sensor(NC), and click Submit.
Scenario 2: Connect the smoke sensor to the AI/DI port on the skylight actuator
(AI/DI_1 is used as an example).
On the WebUI, choose Monitoring > Aisle > Skylight Actuator Group > Skylight
Actuator 1 > Running Parameters, set DI1 alarm level to Low voltage alarm or High
voltage alarm, and click Submit.
Set DI1 alarm level to Low voltage alarm if the smoke sensor is connected over NO; set DI1
alarm level to High voltage alarm if the smoke sensor is connected over NC.
This section describes how to set DI1 alarm severity. For other settings, you can refer to this section.
Normal Connection Status
Smoke sensor AI/DI_1 DI
alarm or DI1_smoke alarm is
displayed on the active alarm
page of the app or WebUI.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
If AI/DI_1 sensor type is set
to Smoke Sensor, power off
and reset the smoke sensor to
clear the alarm.
If AI/DI_1 sensor type is set
to Smoke Sensor(NC), press
the reset button of the smoke
sensor to clear the alarm.
126

Advertisement

Table of Contents
loading

Table of Contents