Functions
Note: We recommend not to select a value that is too low for parameter P22. In particular,
in cases where cooling loads, such as drafts or open windows, affect the control process,
short cycles usually have a negative effect. The heating is directly switched off after the cool-
ing stops.
Note: The set points for room temperature entered in TROVIS-VIEW can be reduced or
raised by 5 K at the room panel (F05 - 1).
Functions
F01 – Control mode
F02 – Selecting the reference variable
F05 – Potentiometer input
Parameters
P01 – Flow temperature set point
P19 – Room temperature set point at rated operation
P20 – Room temperature set point at reduced operation
P21 – Room temperature boost for switch-off
P22 – Time interval flash adaptation
P23 – Pump lag time
6.3

Changing the operating modes

6.3.1 Switchover via binary input

The controller with electric actuator can be configured to allow one of two active binary in-
puts to determine which operating mode is used. Depending on the configuration, the follow-
ing applies:
Binary input BI1:
22
EB 5757-7 EN
F08 - 0
Open binary input BI1 – Rated operation
Closed binary input BI1 – OFF/Frost protection
F08 - 1
Open binary input BI1 – Rated operation
Closed binary input BI1 – Reduced operation
WE
Configuration
1
F01 - 1
0
F02 - 1
0
F05 - 1
WE
Range of values
70 °C
0 to 150 °C
20 °C
10 to 40 °C
15 °C
10 to 40 °C
2 K
1 to 6 K
10 min
0 to 100 min
5 min
1 to 999 min