Troubleshooting
8 Troubleshooting
8.1 No Response to Control Signals
Check 1: Is the control word valid?
If bit 10 = 0 in the control word, the frequency converter
does not accept the control word.
Check 2: Is the relationship between bits in the control
word and the terminal I/Os correct?
Check the logical relationship in the frequency converter.
Define the desired logical relationship in
parameter 8-50 Coasting Select to parameter 8-58 Profidrive
OFF3 Select according to the following range of options.
Select the FC control mode, digital input and/or serial
communication, using parameter 8-50 Coasting Select to
parameter 8-58 Profidrive OFF3 Select.
If parameter 8-01 Control Site is set to digital only, the
frequency converter does not react to commands sent via
8
8
the control word.
Table 8.1 to Table 8.8 show a coast command's effect on
the frequency converter for the full range of
parameter 8-50 Coasting Select settings.
The effect of control mode on the function of
parameter 8-50 Coasting Select, parameter 8-51 Quick Stop
Select, and parameter 8-52 DC Brake Select is as follows:
If [0] Digital input is selected, the terminals control the
coast and DC brake functions.
NOTICE
Coasting, quick stop, and DC brake functions are active
for logic 0.
Terminal
Bits 02/03/04
0
0
1
1
Table 8.1 [0] Digital Input
If [1] Serial communication is selected, commands are
activated only when given via serial communication.
Terminal
Bits 02/03/04
0
0
1
1
Table 8.2 [1] Serial Communication
48
PROFINET
Function
0
Coast/DC brake/Q-stop
1
Coast/DC brake/Q-stop
0
No coast/DC brake/Q-stop
1
No coast/DC brake/Q-stop
Function
0
Coast/DC brake/Q-stop
1
No coast/DC brake/Q-stop
0
Coast/DC brake/Q-stop
1
No coast/DC brake/Q-stop
Danfoss A/S © 04/2017 All rights reserved.
If [2] Logic AND is selected, both signals must be activated
to perform the function.
Terminal
Bits 02/03/04
0
0
Coast/DC brake/Q-stop
0
1
No coast/DC brake/Q-stop
1
0
No coast/DC brake/Q-stop
1
1
No coast/DC brake/Q-stop
Table 8.3 [2] Logic AND
If [3] Logic OR is selected, activation of 1 signal activates
the function.
Terminal
Bits 02/03/04
0
0
Coast/DC brake/Q-stop
0
1
Coast/DC brake/Q-stop
1
0
Coast/DC brake/Q-stop
1
1
No coast/DC brake/Q-stop
Table 8.4 [3] Logic OR
The effect of control mode on the function of
parameter 8-53 Start Select and parameter 8-54 Reversing
Select:
If [0] Digital input is selected, the terminals control the start
and reversing functions.
Terminal
Bits 06/15
0
0
Stop/Counterclockwise
0
1
Stop/Counterclockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 8.5 [0] Digital input
If [1] Serial communication is selected, commands are
activated only when given via serial communication.
Terminal
Bits 02/03/04
0
0
Stop/Counterclockwise
0
1
Start/Clockwise
1
0
Stop/Counterclockwise
1
1
Start/Clockwise
Table 8.6 [1] Serial Communication
Function
Function
Function
Function
MG06G102