Configuration
3.3 Configure the Frequency Converter
3.3.1 VLT Parameters
The following parameters are important when configuring
the frequency converter with a PROFINET interface:
•
Parameter 0-40 [Hand on] Key on LCP. If [Hand On]
is activated, control of the frequency converter
via the PROFINET interface is disabled.
•
After an initial power-up, the frequency converter
automatically detects whether a fieldbus option is
installed in slot A and sets parameter 8-02 Control
Source to [Option A]. When an option is added,
changed, or removed from an already commis-
sioned frequency converter, it does not change
parameter 8-02 Control Source but enters Trip
mode, and the frequency converter shows an
error.
•
Parameter 8-10 Control Word Profile. Select
between the Danfoss frequency converter profile
and the PROFIdrive profile.
•
Parameter 8-50 Coasting Select to
parameter 8-58 Profidrive OFF3 Select. Select how
to gate PROFINET control commands with the
digital input command of the control card.
NOTICE
When parameter 8-01 Control Site is set to [2] Control
word only, the settings from parameter 8-50 Coasting
Select to parameter 8-58 Profidrive OFF3 Select are
overruled and only act on bus control.
MG06G102
Programming Guide