Step 5
Maintenance engineer puts the compo‐
nent into "In service" status
1. Open the diagnostic faceplate.
2. Select the "Maintenance" view.
3. Enter a text in the "Memo" area if
4. Select the "In service" option button
5. Click "On" in the operator panel.
Procedure for deactivating
Step 1
Maintenance engineer completes main‐
tenance
1. Open the diagnostic faceplate.
2. Select the "Maintenance" view.
3. Enter a text in the "Memo" area if
4. Select the "Completed" option
5. Click "On" in the operator panel.
Step 2
Plant operator ends the release for
maintenance
1. Open the technological faceplate.
2. Select the "Parameter" view.
3. Deactivate the "Release for
4. Click "No" in the operator panel.
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA
required.
in the "Status Service" area.
required.
button in the "Status Service" area.
maintenance".
Result
Maintenance of the component can be performed
In the block header, the display for the status of the mainte‐
nance job changes from "Release request" to the status "In
service".
An operator message is generated.
The text entered in the "Memo" area is displayed:
● In the Memo area of the "Maintenance" view of the
faceplate
● As a comment for the message in the operator input list
of the faceplate and message system
Depending on the configuration of the technological block,
the following is displayed on the technological faceplate:
● "Maintenance demanded and Maintenance release" icon
● "Out of service" mode and the "Maintenance demanded
and Maintenance release" icon
Maintenance can be performed.
Result
Maintenance complete
In the block header, the display for the status of the mainte‐
nance job changes from "In service" to the status "Good".
The text in the Memo area is deleted in the "Maintenance"
view of the faceplate.
An operator message is generated.
The entered text in the "Memo" area is displayed as a com‐
ment for the message in the operator input list of the faceplate
and message system.
The "Maintenance demanded and Maintenance release"
icon is hidden in the technological faceplate.
Result
Release for maintenance is ended by the plant operator
An operator message is generated.
The technological block is set to "Manual" mode.