Engineering For Maintenance; Engineering For Release Request - Siemens Simatic PCS7 Function Manual

Process control system maintenance station
Hide thumbs Also See for Siemens Simatic PCS7:
Table of Contents

Advertisement

Configuring the maintenance stations

5.17 Engineering for maintenance

Structure of the file name
The name of the export file is structured as follows:
"<Tagname>_<AssetID>_YYYY_MM_DD_HH_MM_SS_SSS.XML"
Structure of the file name
<Tagname>
<AssetID>
YYYY_MM_DD_HH_MM_SS_SSS Date and time of the export
xml
Additional information
You can find additional information about displaying and exporting the data in the process
control in the section ""Maintenance" view (Page 146)".
5.17
Engineering for maintenance
5.17.1

Engineering for release request

Introduction
You must make interconnections on the blocks in the CFC chart for the release request.
We recommend that the configuration steps be taken into consideration when the typicals are
created.
Requirement
● The CFC typicals have been created.
● The PCS 7 Advanced Process Library V8.2 or higher is used.
Procedure
1. Open the CFC typical.
2. Interconnect the output parameter MS_Req of the channel block with a free input parameter
ExtMsg of the technological block.
3. Change the message class of the utilized external message on the technological block to
the message class not requiring acknowledgment "Request for operator input - General".
4. Adapt the event text as desired.
You can connect the release request signals of multiple channel blocks to the technological
block with an OR operation.
78
Description
Configured name of the component (see rating plate)
Unique, system-assigned identification number of the component
File type
Maintenance Station
Function Manual, 03/2016, A5E36187641-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents