Configuring the maintenance stations

5.7 Configuring the PC station for SIMATIC PDM MS

Procedure
1. In the component view of the SIMATIC Manager, select the multiproject/project into which
you want to insert the MS client.
2. Select the menu command Insert > Station > SIMATIC PC station.
A new SIMATIC PC station is inserted in the selected multiproject/project.
3. Select the SIMATIC PC station, and then select Edit > Object Properties.
4. In the "Name:" input field, enter the name for the PC station.
5. Enter the name in the "Computer name" input field.
– If you are running the MS client on a separate PC station, enter the Windows computer
– If you are operating the MS client as MS client on the engineering station, enter the
6. Click "OK".
7. Select the SIMATIC PC station in the component view of the SIMATIC Manager.
8. In the detailed view, open HW Config by double-clicking the "Configuration" object.
The hardware configuration of the SIMATIC PC station opens.
9. If the hardware catalog is not visible, select the menu command View > Catalog.
The hardware catalog opens.
10.Under "SIMATIC PC Station > HMI" in the hardware catalog, select the WinCC application
client and drag it into the configuration table.
11.Insert other components.
12.Select the menu command Save and Compile Station and close HW Config.
13.In the component view of the SIMATIC Manager, select the "[OSC]" object underneath the
MS client's SIMATIC PC station.
14.Select the menu command Edit > Object Properties.
The "Properties – Client OS: [Name of the OS]" dialog box opens.
15.In the "Name:" input field, enter a name for the WinCC project of the MS client.
16.Click "OK".
5.7
Configuring the PC station for SIMATIC PDM MS
Requirement