Configuring Of Pc Stations For Ms Multiple Station System; How To Configure A Pc Station For An Engineering Station - Siemens Simatic PCS7 Function Manual

Process control system maintenance station
Hide thumbs Also See for Siemens Simatic PCS7:
Table of Contents

Advertisement

Configuring the maintenance stations

5.6 Configuring of PC stations for MS multiple station system

14.If you want to monitor the CP 1623 / CP 1613 communications processor as a network
object, use the "Properties..." button to activate "IP protocol is used" in the object properties
of the CP in the "Interface" area of the "General" tab.
15.Select the menu command Save and Compile Station and close HW Config.
16.In the component view of the SIMATIC Manager, select the "[OS(*)]" object below the
SIMATIC PC station in the "WinCC Appl." hierarchy folder.
* is a number assigned by the system.
17.Select the menu command Edit > Object Properties.
The "Properties – OS: [Name of the OS]" dialog box opens.
18.In the "Name:" input field, enter a name for the WinCC project of the MS single station
system.
19.Select the "Target OS and Standby OS" tab.
– Enter the path to the target OS computer in the "Path to target OS computer" input box.
– Enter a symbolic computer name in the "Symbolic computer name" input box.
– Select ">none>" from the drop-down list box in the "Standby OS" area.
20.Click "OK".
5.6
Configuring of PC stations for MS multiple station system
5.6.1

How to configure a PC station for an engineering station

Introduction
If you have already configured an Engineering Station (ES) in the multiproject/project and are
using SIMATIC PDM, you only have to execute the steps as of step 12.
Requirement
The multiproject/project has been created.
Procedure
1. In the component view of the SIMATIC Manager, select the multiproject/project into which
you want to insert the ES.
2. Select the menu command Insert > Station > SIMATIC PC station.
A new SIMATIC PC station is inserted in the selected multiproject/project.
3. Select the SIMATIC PC station, and then select Edit > Object Properties.
4. In the "Name:" input field, enter the name for the PC station.
5. Enter the Windows name of the ES in the "Computer Name" input box.