Error Texts For Field Devices/User Objects - Siemens Simatic PCS7 Function Manual

Process control system maintenance station
Hide thumbs Also See for Siemens Simatic PCS7:
Table of Contents

Advertisement

Operator control and monitoring
6.11 Faceplate
Additional information
You can find information on error texts in the section "Error texts for field devices/user
objects (Page 180)".
6.11.3.20

Error texts for field devices/user objects

The following table shows possible error texts in the views:
● "Diagnostics" view for field devices (Page 172)
● "Parameters" view for field devices (Page 174)
● "Diagnostics" view for user objects (Page 176)
● "Monitoring" view for user objects (Page 178)
Error code Output In the faceplate
A0040110
Connection to SIMATIC PDM could
80010108
not be established.
Possible causes:
- Archiving is active on the ES
- Communication error
- Access to the project is blocked
A0040001 General error has occurred.
A0040006 Internal error - Incorrect call parame‐
ter
A0040101 Command cannot be run because
PDM Asset Service is being stopped.
A0040102 Command cannot be run because
PDM Asset Service is stopped.
A0040103 Internal error - Error when parsing the
XML transfer parameters
A0040002 Not enough memory.
A0040104 Maintenance path not found or emp‐
ty.
A0040105 Timeout for current command.
A0040106 Internal error - Command could not
be executed
A0040107 Internal error - Timeout for current
command
A0040108 PCS 7 project cannot be opened.
180
Possible measures
Check:
● Whether the ES is accessible via the terminal bus
● Whether an archiving job is running on the ES
Wait until the end of the archiving job.
● Whether the SIMATIC PDM Asset Service is stopped and the
"automatic start/stop" is not activated
Allow the "automatic start/stop".
Start the SIMATIC PDM Asset Service.
A general SIMATIC PDM error is indicated.
Contact Technical Support.
The transferred XML string is incorrectly structured.
Contact Technical Support.
Check whether the SIMATIC PDM Asset Service is currently being stop‐
ped and "automatic start/stop" is not activated.
Allow the "automatic start/stop" and start the SIMATIC PDM Asset Serv‐
ice.
The transferred XML string is incorrectly structured.
Contact Technical Support.
Check whether the error is still indicated after a restart of the ES.
● Check whether the maintenance project is entered correctly in the
settings for SIMATIC PDM.
● Stop and start the SIMATIC PDM Asset Service.
Error in the SIMATIC PDM Asset Service when executing the jobs.
Check whether the error is still indicated after a restart of the ES.
The SIMATIC PDM Asset Service should be stopped, but this is not
possible because jobs are still queued or are still being processed.
● Wait a little longer.
● Then reboot the computer.
● Close SIMATIC Manager on the ES and open the project again.
● Stop and start the SIMATIC PDM Asset Service.