3. Instructions
Unit address
Destination
device
 Unit Addresses
It is also possible to directly specify a serial port (port 1 to 4) within the destination device.
Serial Communications Unit
Serial port 1
Serial port 2
Serial Port Unit Addresses:
• Serial Communications Unit ports
Port 1: 80 + 4 × unit number (hex)
Unit number
Hexadecimal
Decimal
Port 2: 81 + 4 × unit number (hex)
Unit number
Hexadecimal
Decimal
• Serial Communications Board ports
Port 1: E4 hex (228 decimal)
Port 2: E5 hex (229 decimal)
• CPU Unit ports
Peripheral port: FD hex (253 decimal)
RS-232C port: FC hex (252 decimal)
828
CPU Unit
CPU Bus Unit
00 hex
Unit number +10 hex
Node number
Node number
Inner Board
Serial port 1
Serial port 2
0
1
2
3
4
80
84
88
8C
90
128
132
136
140
144
0
1
2
3
4
81
85
89
8D
91
129
133
137
141
145
Inner Board
E1 hex
Node number
CPU Unit
Serial port 2 (Peripheral)
Serial port 1 (RS-232C)
5
6
7
8
9
94
98
9C
A0
A4
148
152
156
160
164
5
6
7
8
9
95
99
9D
A1
A5
149
153
157
161
165
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Computer
01 hex
Node number
A
B
C
D
E
AB
AC
B0
B4
B8
168
172
176
180
184
A
B
C
D
E
A9
AD
B1
B5
B9
169
173
177
181
185
F
BC
188
F
BD
189