Omron SYSMAC CS Series Instruction & Reference Manual page 853

Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Word
Bit
+160
15
Any setting
8 to 11
Communication
Mode
3
Data length
2
Stop bits
0 to 1
Parity
+161
0 to 7
Port
communication
speed
+162
0 to 15
Transmission
delay
+163
0 to 7
Host Link Unit No.
+164
8 to 15
Start Code
0 to 7
End Code
+165
12
Start Code
Specifier
8 to 9
End Code
Specifier
0 to 7
Number of
Bytes of Data
+166
15
Link method
4 to 7
Number of
link words
0 to 3
Maximum
unit number
+167
8 to 15
Response
monitoring
time
0 to 3
Slave unit
number
*1 If "0: Standard" is selected when host link and no-protocol are specified, the settings will be as follows:
• Start bit: 1 bit
• Data length: 7 bits
• Parity: Even
• Stop bit: 2 bits
• Communication speed: 9,600 bits/sec
*2 If "0: Standard" is selected when the peripheral bus and serial gateway are specified, the settings will be as follows:
• Communication speed: 9,600 bits/sec
*3 If NT Link, serial PLC Link (master), and serial PLC Link (slave) are specified, the 00 hex and 0A hex settings are enabled.
*4 If the peripheral bus is specified, the 00 hex and 06 hex to 0A hex settings are enabled.
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Settings
Host Link
0: Standard
*1
Yes
1: Any setting
0 hex: Host Link
2 hex: NT Link
3 hex: No-protocol
4 hex: Peripheral Bus
Yes
5 hex: Host Link
7 hex: Serial PLC Link Slave
8 hex: Serial PLC Link Master
9 hex: Serial gateway
0: 7 bits
Yes
1: 8 bits
0: 2 bits
Yes
1: 1 bit
00: Even
01: Odd
Yes
10: None
00 hex: 9,600
01 hex: 300
02 hex: 600
03 hex: 1,200
04 hex: 2,400
05 hex: 4,800
Yes
06 hex: 9,600
07 hex: 19,200
08 hex: 38,400
09 hex: 57,600
0A hex: 115,200
Units: Bits/sec
0000 to 270F hex:
0 to 99,990 ms
(Units of 10 ms)
00 hex to 1F hex: 0 to 31
Yes
00 to FF hex
00 to FF hex
0: None
1: Use Start Code
0 hex: None (number of Bytes
of Data)
1 hex: Use End Code
2 hex: Set end code to CR+LF
00 hex: 256
01 to FF hex: 1 to 255
0: All station link method
1: Master link method
1 to A hex
0 to 7 hex
00 hex: 5 s
01 to FF hex: 100 to 25,500 ms
(Units of 100 ms)
0 to 7 hex
Communication Mode
Periph-
NT Link
No-protocol
eral Bus
*2
*1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
*3
*4
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
3. Instructions
Serial
Serial PLC
Serial PLC
gateway
Link (master)
Link (slave)
*2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
*3
*3
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
819
3

Advertisement

Table of Contents
loading

Table of Contents