2.3 Working Conditions

Environmental Specifications
Table 2-4 Operation conditions
Item
Operating temperature
Operating humidity
Ambient temperature of
NetCol5000-A025
Ambient temperature of
NetCol5000-A035
Protection level
Altitude
Issue 13 (2019-01-15)
Do not install the smart cooling product near a noise-sensitive place such as an office or a conference
room.
Copyright © Huawei Technologies Co., Ltd.
Specifications
18° C to 45° C
20% RH to 80% RH
Connecting with NetCol500-A032: –20° C to +45° C
(If low-temperature component is used, the lowest
temperature is –40° C.)
Connecting with NetCol500-A036: –20° C to +52° C
Connecting with NetCol500-A038: –20° C to +55° C
Connecting with NetCol500-A036: –20° C to +45° C
(If low-temperature component is used, the lowest
temperature is –40° C.)
Connecting with NetCol500-A038: –20° C to +45° C
Connecting with NetCol500-A072: –20° C to +55° C
Indoor unit: IP20
Outdoor unit: IPX5
0 to 1000 m (If the altitude is greater than 1000 m, the
cooling performance deteriorates.
the derating coefficients.)
2 Product Description
Table 2-6
describes
15