Alar
Alarm
Alarm
m
Severit
ID
y
a111
Hot-aisl
Major
e 1
temp
invalid
Hot-aisl
e 2
temp
invalid
Hot-aisl
e 3
temp
invalid
a112
Hot-aisl
Major
e 1
humid
invalid
Hot-aisl
e 2
humid
invalid
Hot-aisl
e 3
humid
invalid
Hot-aisl
a113
Major
e 1 T/H
brd
comm
failed
Hot-aisl
e 2 T/H
brd
comm
failed
Hot-aisl
e 3 T/H
brd
comm
failed
a116
iCoolin
Major
g
commu
nication
fault
Issue 13 (2019-01-15)
Default
Impact
Value
N/A
The alarm
is
generated
.
N/A
The alarm
is
generated
.
The alarm
N/A
is
generated
.
N/A
The alarm
is
generated
.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Cause
1. Dirt or water exists
around the T/H sensor,
which leads to a
detection fault.
2. The T/H sensor is
faulty.
1. Dirt or water exists
around the T/H sensor,
which leads to a
detection fault.
2. The T/H sensor is
faulty.
1. The cables to the T/H
sensor are loose or
damaged.
2. The DIP switch of the
T/H sensor is set
incorrectly.
3. The T/H sensor is
faulty.
4. The communication
port of the control
board is faulty.
1. The communication
cable is faulty between
the A/C master and
EMS in this MDC.
2. The EMS is faulty.
Solution
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
1. Remove dirt or water
from the T/H sensor.
2. Maintain or replace the
T/H sensor.
1. Check the cables to the
T/H sensor.
2. Set the DIP switch of
the T/H sensor
correctly.
3. Maintain or replace the
T/H sensor.
4. Maintain or replace the
control board.
1. Check the
communication cable
between the A/C
master and EMS.
2. Check the EMS power
supply.
178