Huawei NetCol5000-A User Manual page 78

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Procedure
Step 1 Connect one end of the water sensor cable to the water sensor.
Step 2 Route the other end of the sensor cable through the hole at the bottom of the cabinet and the
hole (the higher one) at the side of the electric control box and connect the two terminals to
the terminal block (X2.9 and X2.10 positions) of the electric control box, as shown in
3-41.
Step 3 Secure the water sensor cable to the cabinet with cable ties.
Figure 3-43
Place the sheet metal of the water sensor upwards and its detection board downwards on the
ground.
Figure 3-43 Routing cables of water sensor (unit: m)
----End
Issue 13 (2019-01-15)
shows the water sensor installation position.
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Figure
69