Huawei NetCol5000-A User Manual page 135

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Step 2 Set the value following Cold-aisle sensor 1 and Cold-aisle sensor 2 to Enable, as shown in
Figure
Figure 4-52 Enabling a humidity and temperature sensor
----End
4.5.9 How to Check Teamwork Control Information
Procedure
Step 1 On the home screen, choose
shown in
Figure 4-53 Teamwork control information screen
Issue 13 (2019-01-15)
This section describes how to enable sensors 1 and 2 in cold aisles.
4-52.
Figure
4-53.
Master/Slave and Active/Standby indicate the information of this single unit. Other information is
about the teamwork control information of the group.
Required cooling capacity: indicates the total cooling/heating requirements of the group and is used
as a reference for enabling the cooling/heating mode by the master device. If the cascade function is
enabled, the capacity is used as a reference for determining whether to start a standby unit.
Copyright © Huawei Technologies Co., Ltd.
>
. The teamwork control information is displayed, as
4 ACC Introduction
126