NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Port
Name
X2.5,
X2.6
X2.7,
X2.8
X2.9,
X2.10
X2.11,
X2.12
X2.13,
X2.14
X2.15,
X2.16
Issue 13 (2019-01-15)
Definit
Function
ion
Port for
Terminals X2.5 and X2.6 are
the
control signal input terminals
outdoor
of an outdoor unit.
unit
on/off
signal
cable
Port for
Terminals X2.7 and X2.8 can
the
be set to remotely shut down
remote
an indoor unit. Specifically, the
shutdo
control signal cable is routed
wn of
from the ports to the
an
monitoring room and control
indoor
the shutdown of the indoor
unit
unit. They are disconnected
before delivery. The
emergency switch for remote
shutdown should be steady on.
Water
The water sensor is connected
sensor
to terminals X2.9 and X2.10.
port
After the water sensor is
installed, the NetCol5000-A
generates an alarm when water
leak occurs.
Smoke
The signal output cables for
sensor
reporting smoke alarms are
port
connected to terminals X2.11
and X2.12. After the smoke
sensor is installed, the
NetCol5000-A generates an
alarm when a fire occurs.
Port for
The signal output cables for
reportin
reporting mains alarms are
g mains
connected to terminals X2.13
outage
and X2.14. When mains outage
alarm
occurs, the NetCol5000-A
generates an alarm.
Reserve
N/A
d
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
Port Feature
N/A
DI input. Can connect to the dry
contact input. Normally open in
normal status and normally closed
when a fault occurs. The dry contact
must be used indoor only, and the
usage range is within 100 meters.
Do not connect two or more units to
one outside dry contact.
The Huawei product is
recommended.
Dry contact port type: normally
open in normal status and
normally closed when a fault
occurs.
Current type: 12 V DC operating
voltage. An alarm is generated
when the operating voltage is
greater than or equal to 3 mA.
The Huawei product is
recommended.
DI input. Can connect to the dry
contact input. Normally open in
normal status and normally closed
when a fault occurs. The dry contact
must be used indoor only, and the
usage range is within 100 meters.
Do not connect two or more units to
one outside dry contact.
N/A
67