Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
displayed.
Figure 4-6 Setting temperature and humidity values
Step 2 Set the parameters by referring to
Table 4-2 Parameter description
Parameter
T/H control type
Issue 13 (2019-01-15)
You are not recommended to modify the parameters not listed in
Description
Sets Cold-aisle,
Hot-aisle,
Return-air, or
Supply-air as
required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Copyright © Huawei Technologies Co., Ltd.
Table
4-2.
Configuration Principle
Return-air: For a hot aisle, select
Return-air to control the temperature and
humidity around the air return vent of the
smart cooling product.
Supply-air: For a cold aisle, select
Supply-air to control the temperature and
humidity around the air supply vent of the
smart cooling product.
Cold-aisle: For a cold aisle, select
Cold-aisle to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Hot-aisle: For a hot aisle, choose
Hot-aisle to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.