NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in
Figure 4-20 Teamwork topology
Table 4-6 Note for the screen
No.
1
2
3
4
Issue 13 (2019-01-15)
2.
Figure
Parameters
On/Off/NA
01, 02, 03
Active/Standby
Frame:
green/non-green
Copyright © Huawei Technologies Co., Ltd.
4-20.
Table 4-6
describes the note for the screen.
Note
On indicates the smart cooling product is started
and Off indicates the opposite. NA indicates the
smart cooling product is offline.
Indicates the device address. 01 is the master one
and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking failed.
Active: properly responds to the requirement
control.
Standby: responds to the requirement control when
Active is faulty (critical alarms, shutdown, and
offline) or Active cannot meet cooling
requirements.
A device with green frame indicates the device
itself, as shown in
A non-green frame indicates the other device in the
group, as shown in
4 ACC Introduction
Step 1
and
. If the
.
.
100