Huawei NetCol5000-A User Manual page 207

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Step 3 Open the U-shaped protection sheet metals of the compressor drive by using Phillips
screwdriver and take it out.
Step 4 Undo the buckle at the groove of the lower baffle plate (shown by 1 in
flat-head screwdriver. Remove the baffle plate and control communications terminals
(terminals with jumpers 12–27 and 12–37 respectively).
Figure 6-14 Compressor Drive Board
(1) Lower baffle plate
Step 5 Push the buckle of the upper baffle plate on the right of the drive inwards using a flat-head
screwdriver until the part of the upper baffle plate (shown by 2 in
free from the buckle. Then move the baffle plate to the right until it is free from the two
buckles on the left. Draw out the baffle plate. Remove the power cables and output signal
cables using a M3 and M6 box-end hex key.
Step 6 Remove the fastener of the input and output cables of the drive.
Step 7 Remove the screws at the four corners of the compressor drive and drag the compressor drive
out, as shown in
Issue 13 (2019-01-15)
Figure
6-15.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure
(2) Upper baffle plate
Figure
6-14) using a
6-14) on the right is
198

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025Netcol5000-a-035

Table of Contents