Huawei NetCol5000-A User Manual page 108

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Parameter
Cooling
capacity
adjustment
period
L1/L2
linkage
cooling stop
ref.temp
L1/L2
linkage
dehumid
stop
ref.temp
L1/L2
linkage
cooling stop
delay
L1/L2
linkage
fastest temp
rise
L1/L2
linkage
temperature
L1/L2
linkage
humdity
Note: In the ACC V100R002C00 software versions, DIP switch is replaced by the
Teamwork CAN resistor enable parameter. If teamwork is not set onsite, remain the
parameter in OFF. If teamwork is set, change the parameters of the first and last units to
ON, and remain the others in OFF.
Issue 13 (2019-01-15)
Description
Adjustment period in L1/L2
linkage PID control.
Reference temperature at
which the smart cooling
product stops cooling in the
cooling mode in L1/L2
linkage.
Reference temperature at
which the smart cooling
product stops dehumidification
in the dehumidification mode
in L1/L2 linkage.
Duration within which the
device is still cooling when the
cooling stop condition is met
in L1/L2 linkage.
Maximum temperature rise
rate when the temperature
rises rapidly caused by sudden
load power increase.
Temperature setpoint in L1/L2
linkage.
Humidity setpoint in L1/L2
linkage.
Copyright © Huawei Technologies Co., Ltd.
Configuration Principle
You are not recommended
to change the value.
Set this parameter based on
the lowest temperature
allowed onsite. Normally
you are not recommended
to change the value.
Set this parameter based on
the lowest temperature
allowed onsite. Normally
you are not recommended
to change the value.
Set this parameter based on
the lowest temperature
allowed onsite. Normally
you are not recommended
to change the value.
Set this parameter based on
the micro-module size and
maximum load power. The
smaller the module and the
higher the load power, the
greater the temperature rise
rate is.
Target temperature
controlled in the
micro-module. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Target humidity controlled
in the micro-module. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
4 ACC Introduction
Default
Value
5s
18.0° C
18.0° C
180s
4.0° C/min
24.0° C
45.0%RH
99