NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Figure 4-19 Teamwork settings screen
Step 2 Set teamwork control parameters.
You can set all the teamwork control parameters on the master smart cooling product but only
Teamwork group no., Teamwork unit address, and Teamwork function on a slave smart
cooling product.
Table 4-5 Teamwork settings
Parameter
Teamwork
group no.
Teamwork
unit address
Teamwork
function
Issue 13 (2019-01-15)
Table 4-5
describes how to set the parameters.
Description
The number of the teamwork
controlled group, which is the
same for all the devices in the
group
Only one device in each group
can be set to 1. Other device
addresses should be different
from each other.
Disable or enable the
teamwork function. If the
teamwork function is disabled,
this device is operating
according to its own control If
the teamwork function is
enabled, this device works in
harmony with others that in
the same group.
Copyright © Huawei Technologies Co., Ltd.
Configuration Principle
Set the assigned teamwork
control number.
Set the assigned unit
address.
Set this parameter based on
the onsite device heat
distribution.
4 ACC Introduction
Default
Value
1
NA
Disable
96