Huawei NetCol5000-A User Manual page 106

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Parameter
Teamwork
mode
Enable
L1/L2
linkage
Network
Total
number of
units
Number of
running
units
Rotation
Rotation
period
Rotation
time
Issue 13 (2019-01-15)
Description
Set the teamwork mode. The
options include Smart and
iCooling.
Enable or disable L1/L2
linkage.
Networking mode for the
teamwork.
Number of the smart cooling
products in this group (1 to 32
can be set).
Number of running units in a
group. The value ranges from
1 to Total number of units.
Disable or enable the active
and standby smart cooling
products to change identity
after a certain time,
maximizing their service life.
Rotation days (1-30).
24 hours in a day (0-23)
Copyright © Huawei Technologies Co., Ltd.
Configuration Principle
Determine whether to
enable the iCooling mode
based on onsite heat load
variations. If the heat load
varies greatly, it is
recommended that you
enable the iCooling mode.
The parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Set this parameter based on
site requirements. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Networked over CAN.
Total number of the smart
cooling products in this
group.
The master unit assigns the
devices to be active units
by the device number,
beginning with the address
1 until to Number of
running units. The rest
will become the standby
ones.
This function is
recommended when the
heat is even.
7 by default.
0 by default.
4 ACC Introduction
Default
Value
Smart
Disable
Over CAN
3
2
Disable
7 days
0