Huawei NetCol5000-A User Manual page 170

In-row air cooled smart cooling product, 600 mm
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Alar
Alarm
Alarm
m
Severit
ID
y
a013
Comp
Critical
dischar
ge HT
lock
a014
Comp
MAJOR -
short
period
a015
Comp
Warnin
exceed
g
runtime
a018
Indoor
Warnin
fan 1
g
exceed
runtime
Indoor
fan 2
exceed
runtime
Humidi
Warnin
a022
fier
g
exceed
runtime
Issue 13 (2019-01-15)
Default
Impact
Value
125° C
The alarm
is
generated
, and the
compress
or shuts
down
forcibly.
The alarm
is
generated
.
30000
The alarm
hours
is
generated
.
40000
The alarm
hours
is
generated
.
3000
The alarm
hours
is
generated
.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Cause
The a012 comp discharge
HT alarm is generated
frequently.
1. The comp starts and
stops frequently,
affected by other
alarms.
2. The load is low, which
leads to the comp
starting and stopping
frequently.
The accumulated runtime
of the compressor exceeds
the alarm thres.
The accumulated runtime
of the fan exceeds the
alarm thres.
The accumulated runtime
of the humidifier exceeds
the alarm thres.
Solution
Reference to the solutions
for the a012 comp
discharge HT alarm.
1. Clear other alarms.
2. Please consult Huawei
technical support.
Maintain or replace the
comp. Tap Maint >
Performance Maint to
clear the accumulated
runtime.
Maintain or replace the
indoor fan. Tap Maint >
Performance Maint to
clear the accumulated
runtime.
1. Maintain or replace the
humidifier.
2. Tap Maint >
Performance Maint
to clear the humidifier
total runtime.
161

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025Netcol5000-a-035

Table of Contents