NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm)
Figure 3-20 Placing the cabinet
1.
2.
Step 7 Adjust the levelness and verticality of the cabinet by raising or lowering the leveling feet.
Step 8 Secure the cabinet.
1.
2.
Issue 13 (2019-01-15)
Place the cabinet on the base and align the mounting holes in the cabinet with those in
the base.
Insert the M12x80 assembly bolts into the holes in the cabinet and base, and partially
tighten the bolts, as shown in
Install the spring washer, large flat washer, and insulation tube on each bolt properly.
Use the torque wrench (M20) to tighten the four bolts to a torque of 45 N•m in diagonal
order, as shown in
Figure
Copyright © Huawei Technologies Co., Ltd.
Figure
3-20.
3-21.
3 Installation Guide
45