Figure 4-16 Changing an SNMP port
Step 6 Click Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
3.
4.
5.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and successfully
identified, click Export File under MIB File to export the MIB file to the USB flash drive for
the customer's use in accessing a third-party NMS.
Issue 13 (2019-01-15)
Click Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
Trap Port is set to 162 by default.
Select the SNMP Version. If an SNMPv3 user is configured, it is recommended that
SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then click
, as shown in
Figure
Figure 4-17 Setting SNMP trap parameters
Click Submit under SNMP Trap.
Copyright © Huawei Technologies Co., Ltd.
4-17.
Figure 4-18
4 ACC Introduction
shows successful file export.