Failed To Access The Unit Through Ip Address & Ioxpress; Failed To Enter System Ready Mode - Moxa Technologies ioThinx 4510 Series User Manual

Hide thumbs Also See for ioThinx 4510 Series:
Table of Contents

Advertisement

ioThinx 4510 Series
Failed to access the unit through IP address & IOxpress
Incorrect network configurations can result in the user not being able to access the unit. Check if the device and
PC are in the same subnet by following the procedure below.
INFORMATION
The default IP address of the device is 192.168.127.254.
This may also occur when you try to configure multiple devices with the same computer. The reason for this
could be that multiple devices have the same default IP address. When sending TCP/IP packets, the packet may
get sent to the wrong MAC address, as it follows the previous record in the computer's ARP Cache. To rectify
this problem, you can erase the ARP Cache records by entering "arp-d" command in the built-in Command-Line
tools.

Failed to Enter System Ready Mode

If the RDY LED stays red, and your web console is not accessible, it means that the system is experiencing an
error. Follow the steps to recover the system.
Step 1: Hold down the RESET button for 30 seconds to trigger the system recovery process. The system will
load the backup firmware and then restart the unit. The system is ready when the RDY LED is green.
Step 2: Open the web console and then update the firmware and configurations to the device.
A-14