Advertisement

Electrical connection
5.4 Cable routing
Route the following cables or carry out the following connection work:
Table 5-4
Cable routing
PROFIBUS cable or PROFINET cable to the Control Unit
DRIVE-CLiQ connections / signal cables to the Control Unit
Signal cables to the customer terminal block –X55
5.4.3.1

Cable routing for PROFIBUS or PROFINET connections to the Control Unit

1. Route the cable for the Control Unit from the bottom left in the cabinet.
2. Remove approximately 3 cm cable insulation from the cable at the height of the shield plate
in the lower section of the cabinet. Attach the cable to the shield plate.
3. Attach the cable by snapping the retaining clamp into the shield plate in an EMC-compliant
fashion.
4. Use cable ties to secure the cable at appropriate locations.
5. Feed the cable up through the cabinet and, at the height of the Control Unit, route it directly
up and to the right towards the Control Unit. Route the cable corresponding to the standard
cable prerouted in the cabinet.
6. Use cable ties to secure the cable at appropriate locations.
7. Connect the cable to the Control Unit.
Information regarding connecting the cable is provided in the "Control cabinets and
supplementary system components" manual.
5.4.3.2

Cable routing for DRIVE-CLiQ connections and signal cables

1. Route the DRIVE-CLiQ/signal cable from the bottom left in the cabinet.
2. Use cable ties to secure the cable at appropriate locations.
3. Feed the cable up through the cabinet and, at the height of the Control Unit, route it directly
up and to the right towards the Control Unit. Route the cable corresponding to the standard
cable prerouted in the cabinet.
4. Use cable ties to secure the cable at appropriate locations.
5. Connect the DRIVE-CLiQ/signal cable to the Control Unit.
5.4.3.3

Cable routing to the customer terminal block -X55

1. Route the cable for the customer terminal block from the bottom left in the cabinet.
2. Remove approximately 3 cm cable insulation from the cable at the height of the shield plate
in the lower section of the cabinet. Attach the cable to the shield plate.
3. Attach the cable by snapping the retaining clamp into the shield plate in an EMC-compliant
fashion.
4. Use cable ties to secure the cable at appropriate locations.
88
Checklist for cable routing and connection work
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
Completed?