Servicing

8.4 Cleaning

8.3.4.3

Maintaining the pumps

Check the pumps every three months for smooth running, leaks and normal housing
temperatures. If the pumps leak, then please contact Technical Support (Page 139).
8.3.4.4

Maintaining the fans of the additional cooler

Perform a visual inspection every three months. During the visual inspection of the fans, check
for smooth running and normal housing temperatures.
The average service life of the fans is approximately 50,000 hours. However, the actual service
life depends on additional influencing quantities, for example, the ambient temperature and
cabinet degree of protection. As a consequence, the service life can deviate from this value
on a case-for-case basis.
Replace the fan in a timely manner in order to maintain the availability of the drive.
See also
Replacing the fan of the additional cooler (degree of protection IP54) (Page 129)
8.4
Cleaning
8.4.1

Removing dust deposits

Remove dust deposits at least once per year. You can use an ESD brush or an ESD vacuum
cleaner. The ventilation openings in the cabinet must never be obstructed.
NOTICE
Cleaning fiber-optic cables and electronic components with a damp rag
Fiber-optic cables, fiber-optic cable bundles and electronic components can be damaged if
cleaned using a damp rag.
If the components are very dusty, remove the dust using a dry, lint-free cloth. In so doing, do
not bend the fiber-optic cables.
8.4.2

Cleaning frame components

Use a dry, clean, lint-free ESD cleaning cloth. Wipe all external parts of the rack with it. Make
sure that the dirt is not distributed, but actually removed by constant changes of the wiping
surface of the cloth. For severe pollution, use a cleaning cloth soaked in ethyl alcohol, but not
to the extent that the alcohol drips.