Siemens SINAMICS S120 Operating Instructions Manual page 102

Applications for cabinet modules, liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
6.2 Commissioning the cooling unit
Status signals of the cooling unit
The following status signals are sent from the cooling unit to the converter:
Status signal
Cooling unit ready
● Low = cooling unit not ready
● High = cooling unit ready to switch on. You can start
Cooling unit operates correctly.
● The cooling unit operates correctly after switch-on.
● The coolant temperature lies within the correct
Group alarm
● High = no alarm active
● Low = at least one alarm message is active
Group fault
● High = no-fault active
● Low = at least one fault is active
102
the converter.
A pump is running.
The water pressure and the water level match the
specifications.
range.
Function name
DI0
DI1
DI3
DI3
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
TM31 terminal
-X520:1
-X520:2
-X520:3
-X520:4