Specification Of The Untreated Water - Siemens SINAMICS S120 Operating Instructions Manual

Applications for cabinet modules, liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

B.2

Specification of the untreated water

Designation
Temperature range
Water pressure
Sea water
Permitted water impurities
Size of entrained particles
Dissolved solids
Hydrogencarbonate
Sulfate
Hydrogencarbonate/sulphate
Electrical conductivity
pH value
Ammonium
Chloride
Free chlorine gas
Sulphite
Hydrogen sulfide
Free (aggressive) carbonic acid
Total hardness
Nitrate
Iron
Aluminum
Manganese
Siemens Drives & PLCs
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
B.2 Specification of the untreated water
Value
+5° C ... +38° C
recommended temperature range:
+25° C to +30° C
min. 1.8 bar ... max. 6.0 bar
recommended water pressure: 2.5 bar
No
<1.0 mm
<350 mg/l
70 ... 300 mg/l
<70 mg/l
>1.0
10 ... 500 µS/cm
7.5 ... 9.0
<2 mg/l
<300 mg/l
<1 mg/l
<1 mg/l
<0.05 mg/l
<5 mg/l
4,0 ... 8.5 dH
<100 mg/l
<0.2 mg/l
<0.2 mg/l
<0.2 mg/l
Technical data
143

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents