B Technical Data; General Technical System Data - Siemens SINAMICS S120 Operating Instructions Manual

Applications for cabinet modules, liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Technical data
B.1

General technical system data

General data
Line voltages and power ranges
Line system configurations
Line frequency
Output frequency
Line power factor fundamental
factor
Efficiency
Control method
Fixed speeds
Speed ranges that can be skipped 4, parameterizable
Braking operation
Degree of protection
Protection class
Overvoltage category
Degree of pollution
Cooling type
Touch protection
Cabinet system
Paint finish
Weight
Power data for the basic version, power rating can be increased using a parallel connection.
1)
Siemens Drives & PLCs
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
3 AC 380 V ... 480 V, ±10 % (-15 % < 1 min), 4.8 kW ... 800 kW
3 AC 500 V ... 690 V, ±10 % (-15 % < 1 min), 55 kW ... 1200 kW
Line supplies grounded at the neutral point (TN/TT supply systems) or non-grounded line
supplies (IT supply systems)
47 ... 63 Hz
Vector control: 0 ... 600 Hz
Servo control: 0 ... 650 Hz
U/f control: 0 ... 650 Hz
Basic Line Modules:
> 0,96
> 99,0 %
Servo control, vector control with and without sensor or U/f control
15 fixed speeds plus 1 minimum speed, can be parameterized
With regenerative feedback or by additional Braking Modules and braking resistors
IP20, IP21, IP23, IP43 and IP54
(with side panel, right or left)
Protection class I acc. to EN 61800-5-1
III according to EN 61800-5-1
Limiting overvoltages
For line supplies with a grounded line conductor and a line voltage > 600 VAC, line-side
components must be installed to limit overvoltages to overvoltage category II according
to EN 61800‑5‑1.
2 according to EN 61800-5-1
Forced air cooling AF + WE + AN according to EN 6014
BGV A 3 acc. to EN 50274
Rittal TS 8, doors with double-bit key, tripartite base plates for cable inlet
RAL 7035 (indoor requirements)
The relevant weight of a cabinet unit is specified on the test certificate supplied and on
the rating plate. The specified weight corresponds to the actual expansion stage of the
cabinet unit
Smart Line Modules:
> 0,96
> 98,5 %
B
1)
1)
Active Line Modules:
Adjustable (set in the facto‐
ry to cos φ = 1)
> 97,5 %
141