Advertisement

Note
If an incorrect phase sequence was connected during the cable installation and it cannot be
corrected by a subsequent swapping of the motor cables, you have two possibilities:
● Change the phase sequence by entering a negative setpoint.
● Change the phase sequence with the drive parameterization.
Note
Interconnect the windings for motors that can be operated in star-delta correctly. To do this,
read the motor documentation. Observe the required isolation voltage for the operation of the
drive.
5.3.3

Line/power connections

Line Connection Modules
Table 5-2
Terminals
U1/L1, V1/L2, W1/L3
3-ph. AC power input
Motor Modules in chassis format
Table 5-3
Terminals
DCP, DCN
DC power input
U2/T1, V2/T2, W2/T3
3-ph. AC power output
Siemens Drives & PLCs
Applications for Cabinet Modules, liquid cooled
Operating Instructions, 04/2015, A5E35974555A
Line/power connection of the Line Connection Modules
Technical specifications
Voltage:
380 V AC, 3-phase –10% to 480 V AC, 3-phase +10% (-15% < 1 min)
500 V AC, 3-phase –10% to 690 V AC, 3-phase +10% (-15% < 1 min)
Connecting thread:
M12/50 Nm or M16/115 Nm for ring cable lugs in accordance with DIN
46234
DC link / motor connection of the Motor Modules
Technical specifications
Voltage:
510 to 750 VDC
675 to 1035 VDC
Voltage:
0 V 3-ph. AC to 0.72 x DC link voltage
Connection:
M12/50 Nm or M16/115 Nm for ring cable lugs in accordance with DIN
46234
Electrical connection
5.3 Connection
83