Checklists and forms
C.2 Electrical installation: Checklist
Activity
Cabinet operation from a higher-level control system / control room.
● The control cables are connected in accordance with the interface assignment and
the shield is connected.
● To prevent interference, the control cables are routed separately away from the power
cables.
● The relevant EMC directives have been taken into account (Chapter "Electrical
connection")
DRIVE-CLiQ cables
Optional components
CBC10 Communication Board
CBE20 Communication Board
TM150 Temperature Sensor Mod‐
ule
Safety license for 1 to 5 axes
Sensor Module
SMC10
SMC20
Sensor Module
148
All DRIVE-CLiQ cables are correctly connected.
The permissible cable lengths are complied with.
("S120 Commissioning Manual, Rules for wiring with
DRIVE-CLiQ"
)
("S120 Equipment Manual for Booksize Power Units,
DRIVE-CLiQ Cabinet Gland" and "S120 Equipment
Manual for Booksize Power Units, DRIVE-CLiQ Cou‐
pling")
The supplied CBC10 is installed in the factory in the
option slot of the Control Unit.
(S120 Cabinet Modules / Options / G20, Commu‐
nication Board CBC10 Manual).
The supplied CBC20 is installed in the factory in the
option slot of the Control Unit.
Remove the CBE20 in a no-current state and note
down the MAC address. Install the CBE20 into the
option slot again.
("SINAMICS S120 Cabinet Modules / Options /
G33, Communication Board CBC20" Manual).
A maximum of 12 temperature sensors (PT100,
PT1000, KTY84, PTC, bimetallic NC contact) are
connected to the TM150 Terminal Module.
("SINAMICS S120 Cabinet Modules / Options / G51
to G54, Temperature Sensor Module TM150" Man‐
ual).
The safety licenses are activated.
("SINAMICS S120 Cabinet Modules / Options / K01
to K05, Safety License for 1 to 5 axes).
The correct encoders are connected to the SMC10
Sensor Module.
("SINAMICS S120 Cabinet Modules / Options / K
46, Sensor Module Cabinet-Mounted SMC10" Man‐
ual).
The correct encoders are connected to the SMC10
Sensor Module.
("SINAMICS S120 Cabinet Modules / Options / K
48, Sensor Module Cabinet-Mounted SMC20" Man‐
ual).
Available/performed?