Parameters available for the easy setup
The parameters provided in the following tables are available for the easy setup.
These parameter are only shown, if theeasySetup = 1 parameter is set. These parameter are
not shown, if theeasySetup = 0 parameters are set.
Which parameter is shown depends on which system diagram has been selected and which
heat pump types are indicated. Customized settings are automatically applied after the initial
loading of the system diagram via cold start = 1 for the parameter of the respective control
circuit.
Explanation for the tables
Name:
Information text: Long term of parameters
Unit:
St-SP:
Min.:
Max.:
Remark:
Heat pumps 1 to 3
Name
Information text
Heat pump 1
maxSP
max. setpoint
boost.hCu
Heating circuits boost
BoosterH
Domestic hot water electric
heating element
BoostDel
Time delay domestic hot water
E-heat
Cooling
Cooling mode
pumpRotRate
Pump rotation speed
Cooling
Cooling demand via heat pump
release
CAPRAN-WP1
Heat pump 2
Heat pump 3
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Short term for parameter
Measuring unit for the parameter
Ex-works set standard setpoint for the parameter
Minimum value for the parameter
Maximum value for the parameter
further information about the parameter
Unit
St-SP Min.
°C
70.0
°C
0.0
0
min
60
0
4
0
Max.
Remark
30.0
90.0 Setpoint limitation
0.0
10.0 Increase of demand (heat/cool)
0
1 available 0: no; 1: yes
20
95 Switch on delay for the domestic hot water
e-heating element
0
1 1: Cooling operation permitted (only genera-
tion "F")
0
7 (only generation "F")
0
1 0: no 1: yes
D03
X16 only on All in One models (type-HP1=ADCx):
set the type and performance of the outdoor
unit; D03/05/07/09/12/16: High Performance
range, X09/12/16: T-CAP range
see heat pump 1