Panasonic Aquarea PAW-HPM1 Installation And Commissioning Manual page 21

Heat pump manager (hpm)
Table of Contents

Advertisement

9
Continue Step 9
Perform settings for "Solar system + Domestic hot water tank" (if available)
9-7
9-8
9-9
9-10
9-11
9-12
9-13
9-14
→ Domestic hot water Solar, P. 82
Perform settings for "Solar system + Buffer tank" (if available)
9-15
9-16
9-17
9-18
9-19
9-20
→ Buffer Solar, P. 83
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Name
Information text
solColl
Solar collector temp.
solTank
Solar tank temp.
solPu
Solar pump
TDiffSolOn
Temp. difference solar pump
on
TDiffSolOff
Temp. difference solar pump
off
maxTSolTa
max. temperature Sol.-tank
sensor
maxTcoll
max. temperature collector
sensor
collFrLim
Frost.lim collector
Name
Information text
solColl
Solar collector temp.
solPu
Solar pump
tDiffOn
Temp. difference solar on
tDiffOff
Temp. difference solar off
maxTsolar
max. temp. Solar circuit
solFrLim
Frost limit
Easy Setup Overview
Standard
Remark
setpoint
0
Assign available input terminal
(17 - 24) e.g. terminal 24;
0
optional: assign solar buffer sensor
(otherwise: DHW tank sensor);
Assign terminal
0
assign available output terminal: e.g.
terminal 9
8.0 K
2.0 K
70.0 °C
110.0 °C
–10.0 °C
Standard
Remark
setpoint
0
Assign available input terminal (17 -
24) e.g. terminal 24;
0
assign available output terminal: e.g.
terminal 9
8.0 K
2.0 K
90.0 °C
–10.0 °C
3
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquarea paw-hpm2