Page 1
Planning Instructions MEW01472 Revision - Fire Alarm System EBL512 G3 United version 2.7.x Author: Jan Pettersson Date of issue: 2012-04-05 Date of rev:...
Page 2
This page has deliberately been left blank.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Table of contents Introduction________________________________ 9 Definitions / Explanations ___________________ 11 PEWN AB _______________________________________ 11 Alarm points _____________________________________ 11 2.2.1 Smoke detector _______________________________ 11 2.2.2...
Page 4
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 3.5.4 Web512 II Config Tool 2.7 ______________________ 17 Control Unit / TLON Network _______________ 18 The TLON network ________________________________ 18 Single TLON Network / Redundancy in distributed system _ 18...
Page 5
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 9.3.1 Web-servers __________________________________ 57 Other units _______________________________________ 57 9.4.1 Alert Annunciation Controllers ___________________ 57 9.4.2 External LED ________________________________ 58 9.4.3 Alarm devices (sounders, etc.) ___________________ 58 9.4.4...
Page 6
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 14.4 Interlocking control expressions ______________________ 82 Fire Door Closing __________________________ 83 Functions / Services / Features _______________ 84 16.1 Sensor value _____________________________________ 84 16.2...
Page 7
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.25 Service signal _________________________________ 105 16.26 Fault signal (fault condition) ______________________ 106 16.27 Alarm texts ___________________________________ 106 16.27.1 Creating the alarm texts via Win512 version 2.7.x _ 107 16.27.2...
Page 8
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 20.1.1 General data ________________________________ 129 20.1.2 Type of control unit ___________________________ 129 20.1.3 LED indications by inputs ______________________ 130 20.1.4 Miscellaneous _______________________________ 130 20.1.5...
Page 9
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Power supply _____________________________ 152 26.1 Charger functions ________________________________ 153 26.1.1 Charging ___________________________________ 153 26.1.2 Battery charging functions: _____________________ 153 26.1.3 Security functions ____________________________ 153 26.2...
Page 10
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x...
2.7.x. On the date / revision date of the document x = 0. EBL512 G3 S/W United version 2.7.x. is a bit special since it can be used only for EBL512 G3 units in a TLON Network with both EBL512 units and EBL512 G3 units, i.e.
Page 12
MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x a product name (e.g. EBL512 G3 CU, 128 alarm points, with printer) A HW (e.g. a printed circuit board) has: a type number (e.g. 5010) ...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. PESN AB Panasonic Eco Solutions Nordic AB Alarm points Units, which can generate a fire alarm (in the control unit), i.e.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 2.2.8 Conventional zone line input / External line Input intended for one or more conventional alarm points. End-of-line device in the last alarm point on the line.
LCD (320 x 240 dots) with backlight. 2.16 Door open (Door / Key switch) In EBL512 G3 there is a door switch, which is activated when the control unit's door is open. In the ext. FBP 1828 this door switch is replaced with a key switch.
EBL512 units (1548 / 1549 / 1550) with software EBL512 version 2.7.x together with EBL512 G3 units (5000 / 5001) with software United version 2.7.x in a TLON Network, i.e. a mixed system. EBL512 G3 united version 2.7.x can only be used in a mixed system.
2 and 4. The Swedish front conforms to SS3654. 3.1.1 Printer The control unit EBL512 G3 type 5000 can be delivered with a printer ("PRN" included in the article number) or without a printer. In Ext. Fire Brigade Panel 1826 it is possible to mount an optional Printer 1835.
Start with one control unit and then later when it is required, add more units. The TLON network makes it possible to install the control units in one building or in many buildings. PC software (S/W) The following PC software is used together with the EBL512 G3 system. 3.5.1 Win512 version 2.7.x Win512 version 2.7.x is used for programming and commissioning of...
download S/W & EBL512 settings in an EBL512 C.U. NOTE! For the EBL512 G3 control units in a mixed system, Win512 version 2.7.x has to be used to download S/W. Old SSD files can be opened in a newer (higher) version of Win512, saved, edited and thereafter downloaded to an EBL512 G3 / EBL512 control unit with the corresponding version.
Control Unit / TLON Network The TLON network In a mixed system, up to 30 control units (EBL512 G3 United version 2.7.x and EBL512 version 2.7.x) can be connected in a TLON Network. At least one has to be an EBL512 control unit.
Page 21
EBL512 units a mixed system, i.e. a system with both EBL512 units and EBL512 G3 units. EBL512 G3 United version 2.7.x can only be used in a mixed system. As an alternative the I/O unit 3361 zone line input can be used.
Printer cannot be mounted. Figure 1. Left: The EBL512 G3 Control Unit 5000, with printer. The look might vary according to configuration, etc. Right: The EBL512 G3 Control Unit 5001. The control unit is housed in a grey metal cabinet. Depending on country, convention, configuration, etc.
Page 23
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Figure 2. The EBL512 G3 front with display ("Man-Machine- Interface"); The Fire Brigade Panel (FBP) is the upper part and the Control Panel (CP) is the lower part. The look might vary depending on the language, country, etc.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Each control unit 5000-5001 has the following basic configuration: Grey metal cabinet MMI board (5011) (not in 5001) EBL512 G3 front with display (not in 5001) ...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x a Mounting plate for inflammable wall 5021, which can be provided with cable glands. COM loops Each control unit has four COM loops (0-3) to which the loop units are connected.
Page 26
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x - The control unit (an algorithm) will now try to re-enable the first isolator (sequence no. 0) in the A-direction. If this is possible the next isolator (sequence no.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Programmable voltage outputs (S0-S3) The 24 V DC outputs are supervised (monitored) Connections according to dwg 512 G3 – 23. When all connections are done a calibration has to be performed, see chapter "Calibration of supervised...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Relay outputs for routing equipment (tx) Not programmable outputs. The outputs can be tested via menu H1, see the EBL512 G3 Operating Instructions MEW01473. Connections according to dwg 512 G3 –...
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Expansion boards 458x Inside EBL512 G3 (5000 and 5001) there are space and holders for up to six optional expansion boards of the types 4580 and 4581 to be mounted, see drawing 512 G3 - 01. A ribbon cable 5089 shall be used for connection of up to six expansion board(s) to the main board.
Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x NOTE! NOTE! NOTE! NOTE! NOTE! In Win512 version 2.7.x the following is valid for an EBL512 G3 control unit: 4580 boards have to be programmed as 1580 boards.
6.2.1.3 Alarm from control unit This option cannot be used for an EBL512 G3 control unit. 6.2.1.4 EX zone line input (EOL resistor) This option is not available for an EBL512 G3 control unit.
Page 32
This activates a fire alarm in EBL512 G3. In this state short-circuit, open circuit, high current and low voltage states cannot be reached / activated. After alarm reset (in EBL512 G3) the zone line input will return to the normal state. 6.2.2.4 Short-circuit state...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Logic, i.e. normally open (NO) or normally closed (NC) contacts Control expression (one or more trigger conditions) For more information, see chapter "Programmable outputs", page 64.
/ address (0-7) is set with jumpers (JP1-JP3) on the I/O Matrix board respectively. See Figure 5, page 28. In EBL512 G3 can totally up to 200 outputs be used, including all kinds of outputs. For more information (e.g. application board type selected via jumpers JP4-JP5), see the I/O Matrix board 4582, Technical description MEW00914.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Each output (0-47) has to be added and programmed via Win512 version 2.7.x regarding: Output no. (0-47) Properties, like any programmable relay output.
External FBP / DU interface board 1587 One 1587 board has to be programmed when Display Units type 1728, 1735, 1736, 1826 and 1828 shall be connected to an EBL512 G3 control unit with S/W United version 2.7.x, i.e. connected in a mixed system.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Printer The control unit type 5000 can be with or without a printer depending on if "PRN" is added in the article number or not. It is mounted on the front panel door and is connected to the MMI board 5011.
Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x TLON connection board 1590/5090 On the EBL512 G3 control unit (5000 / 5001) main board (5010), there are spaces and connectors for two TLON connection boards type 1590/5090 A single (standalone) EBL512 G3 United version 2.7.x control unit is...
The following units can be connected to the COM loops (in NORMAL mode, except 4313 and 4370 that has to use 2330 mode): WinG3 version 1.1.x has to be used to download the EBL512 G3 software version 1.1.x. Change the number of addresses. This action requires a special download password.
Page 40
4593 only. (listed below) can be found in old installations and Discontinued units the following can be used in EBL512 G3United version 2.7.x installations as well. NOTE! The red "Strikethrough" units cannot be used in EBL512 G3 United version 2.7.x.
Each COM loop unit has to have a unique COM loop address (001- 127). This address and the mode are set with an Address Setting Tool (3314). For EBL512 G3 is always the NORMAL mode to be used (default). 9.1.1...
Page 42
The Address setting tool (3314) is also used for mode setting: NORMAL mode: Used for 4313 in system EBL512 G3. 2330 mode: Used for EBL512 G3 United version 2.7.x in a mixed system. 2312 mode: Not used in a mixed system.
Page 43
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 3339 Enclosed Addressable Manual Call Point. 3339 is like the 3333 unit but with another type of back-box (incl. a tightening gasket). For surface mounting. For indoor use in premises where IP56 rating is required.
Page 44
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Shall be plugged in an analog base (3312 / 3312F / 3312FL / 4313). Built-in LEDs are lit to indicate that the detector activated a fire alarm.
Page 45
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 60 Smoke value Figure 8. When the calculated value in the decision algorithm exceeds the lower graph, pre-warning will be activated.
Page 46
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 2312 mode: 4301 + base 3312 is in this mode an analog photoelectric smoke detector and can be a spare part for 2304 + base 2312.
Page 47
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 6295 Heat detector: Enclosed (IP67) Fixed temperature heat detector, 57°C, class A2 S (static response temp. range 54- 70°C), latching. Min./typical/max. ambient temp. -40/+25/+50°C. Built-in LED is lit to indicate that the detector has activated a fire alarm.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x "technical address", etc. to be read also when the detector is plugged in its base. 100 label holders per packet. Excl. labels.
Page 49
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x address label on which the unit's COM loop address can be written. The Address setting tool (3314) is also used for the mode setting: NORMAL mode: Used for 3361.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x technical address can be written. The Address setting tool (3314) is also used for mode setting: NORMAL mode: Used for 3364. 2330 mode: Not used.
The Address setting tool (3314) is also used for mode setting: NORMAL mode: Used for 4313 in system EBL512 G3. 2330 mode: Used for EBL512 G3 United version 2.7.x in a mixed system. 2312 mode: Not used in a mixed system.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Segment A Segment B A-dir. 4313 no. A no. 00 EBL512 G3 4313 no. B no. 01 B-dir. Segment C Figure 9.
Conforms to EN54-4. 3366 is connected to a COM loop, i.e. it is monitored from EBL512 G3 and e.g. loss of the main power source will generate a fault in EBL512 G3. It can be used as power supply for external...
Page 54
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 3364 unit (see page 47). It also has a "/Mains OK" output (normally low), intended to be connected to the corresponding input on the 3364 unit.
The display and the push buttons (in the unit respectively) are used to set the address, which also can be changed via EBL512 G3. The S/W mode shall be set to xxxx – 1587 (xxxx = type number). See the Technical Description for the unit respectively.
Page 56
Alert Annunciation Units When the Alert Annunciation (AA) function shall be used in system EBL512 G3, a unit is required for the related manoeuvres, i.e. to acknowledge / reset the AA alarms. For a detailed description of the Not valid for the Swedish convention (SBF).
Win512 version 2.7.x. A built-in buzzer will sound to indicate a not acknowledged AA alarm. New software versions can be downloaded directly in the unit. The unit is power supplied from EBL512 G3 or an external power supply. The unit has the following LEDs: Fire and Alarms queued, indicating fire / AA alarm.
Win512 version 2.7.x. Furthermore, at least 617 texts can for selected fire alarms be stored in the unit and will in such a case be shown, instead of the texts sent out from EBL512 G3 for these alarms. These text messages will be downloaded to the unit via Win512 version 2.7.x.
Alert Annunciation Controller (AAC). This unit has no display, i.e. it has to be mounted close to EBL512 G3 (or an ext. FBP) where the fire alarms will be presented. The compact size enclosure (HxWxD, 145 x 220 x 50 mm) is made of grey high impact ABS.
Alarm devices (sounders, etc.) Regarding addressable alarm devices, see page 48. In the Panasonic product range are no alarm devices intended for a supervised (monitored) voltage output (e.g. S0 – S3 in EBL512 G3). Connections of alarm devices according to drawings 512 G3 – 23 and -38.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x (e.g. 1N4004) in parallel with the coil, like in the alarm devices, see drawing 512 G3 - 23. 9.4.5 Boxes 3362 Waterproof box (IP66 / 67). A grey polycarbonate box with ingress protection rating IP66 / 67.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Programmable inputs In each control unit are four programmable, not supervised inputs (I0-I3) available. On the COM loops can be connected the addressable multipurpose I/O unit 3361 with two programmable inputs.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Input programming Input programming is done in Win512. For more information see Win512 help. Each input has to have an individual Trigger condition ("Triggered by") and Logic.
Page 64
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Comments to the trigger conditions: 0. Default. The input does not work. 1. Key cabinet, where the fire brigade store there key to the building.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 15. "Loss of main power source to external power supply equipment" fault output will activate a fault in the EBL512 system. It will have the same time delay, as set for the Loss of main power source fault for the c.i.e.
In each control unit are four programmable voltage outputs (S0-S3) and two programmable relay outputs (R0-R1) available. 8 relays expansion boards (4581) can be mounted in each EBL512 G3. See chapter "Expansion boards 458x", page 27. On the COM loops can be...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Control unit outputs S0 – S3 12.1 Each control unit has four programmable, supervised (monitored) voltage outputs: Supervised (monitored) voltage output, 24V DC, max. 500 mA (Fuse F4) Supervised (monitored) voltage output, 24V DC, max.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Connections and more information, see dwg. 512 G3 – 34. 12.4 The 3361 unit's Outputs Re0 & Re1 Each 3361 unit has two programmable relay outputs. Relay contact ratings: 30 V DC (125 V AC), 2A.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Output programming Output programming is done in Win512 version 2.7.x. See the Win512 version 2.7.x dialog box respectively. 13.1 Type of output Some output types can be collectively disabled.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 13.2 Logic (•) Normally open / low Normally open relay contact or normally low voltage output. ( ) Normally closed / high Normally closed relay contact or normally high voltage output (24V DC).
Page 71
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Times: Delay time (when required) Pulse length time (when required) Pulse off time (when required) De-activation time (when required) Regarding the programming, see chapter "Time activation output",...
Page 72
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x In EBL512 G3 COM loop units Output S0-S3 4581 I/O unit Unit Siren, 4582 Inter S/B & 3361 3364 board locking board...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 13.5 Control expression Each programmable output has to be given a control expression. It is created by so called Boolean algebra. Trigger conditions (see "Available functions"), logical "Operators"...
Page 74
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Consecutive Heavy Smoke Alarm (sequence) (+start Zone no. and address +stop Zone no. and address +Quantity) Two Address Dependent Fire Alarm (+Zone no.
Page 75
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Comments to the trigger conditions (functions): Fire alarm. For more information, see EBL512 G3 United version 2.7.x Operating Instructions. See 1. See 1.
Page 76
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Loss of mains (in a c.i.e. or output unit 2262). NOTE! The output(s) will be activated immediately but the corresponding fault is normally delayed.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Service signal is activated (by any sensor). Due to revised encapsulation function this trigger condition has no function. (It will never be true.)
Page 78
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 13.5.3.2 a OR b OR c=y y is true if at least one of the conditions a, b, c is true, i.e. a=1 or b=1 or c=1 makes y=1.
Page 79
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 13.5.3.3 Inverts a condition, e.g. NOT b = NOT 0=1. a OR NOT b AND c = y This is shown in the following table: 13.5.3.4...
Page 80
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Here follows some examples (and explanations) to show the principles how to build a control expression with "conditions" and logical operators.): Example 1...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Interlocking function The interlocking function is used to verify that an output really is activated, i.e. by "combining" an output with an input (feed-back from the equipment controlled by the corresponding interlocking output).
Page 82
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Figure 16. Win512 version 2.7.x "Interlocking Combination" dialog box. Name: Displayed in the Win512 version 2.7.x Tree and List views. Default is "Interlocking Combination" that can be edited when wanted / required.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Latched output checked = Output reset has to be performed via menu H9/C3. (Automatically output reset will not take place when the control expression becomes false.).
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The "Interlocking Combination" (Area / Point) is to be entered to activate the output. The corresponding interlocking input will be "monitored" in the same way as if the output was activated by its control expression.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Fire Door Closing Programmable outputs can be used for fire door closing. A special trigger condition is available (Fire Door Closing.). Type of output is normally "Control, neutral".
Some Functions / Services / Features require programming in Win512 version 2.7.x, see chapter "PC software (S/W)", page 16. For more information see also EBL512 G3 United version 2.7.x Operating Instructions MEW01473. How to connect the PC and more information, see EBL512 G3 United version 2.7.x Operating...
Service level (D). "Sensor Information" is available via menu H4/U4. Via Win512 version 2.7.x and a PC connected to EBL512 G3 United version 2.7.x you can get "Sensor Information" for all analog detectors on a COM loop or an individual detector. For an individual detector you can also get continuous information: Technical no.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x than for fire alarm, i.e. pre-warning will be activated before the fire alarm from the same alarm point. 3. heavy smoke alarm will be activated at a higher level (bigger offset) than for fire alarm, i.e.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x low sensitivity during daytime (i.e. the alternative alarm algorithm is used to reduce nuisance alarms during working hours). The alarm algorithm in use can be read in menu H4/U4.
Page 90
In this example, alarm algorithm "N-15" is selected, i.e. normal detection time 15 sec. and normal sensitivity 3% (30). X = 5. The detector polling time t ≈ 2.56 sec. (In system EBL512 G3 United version 2.7.x the detector polling time t ≈ 4 seconds and the step value "X"...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The decision value has here reached the pre-warning level and pre-warning is activated. The decision value is here below the pre-warning level and the pre-warning is automatically reset.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Figure 20. An example of the smouldering smoke algorithm for an Analog smoke detector 4301. Explanations to the figure: In this example, the week average sensor value and the decision value are "10"...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x and max. sensor values. All three values should be studied together. (E.g. one or two high sensor values will not result in a high performance factor.) The performance factor is calculated for each...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.6.1 Class A1 algorithm Conforms to Class A1. Typical / max. application temperature 25 / 50° C. Max. / min. static response temperature 54 / 65° C.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x FAULT: Loop unit zone: xxx addres:xx Technical number xxxxxx 16.8 Minimum / Maximum sensor values To find out how the environment is, where an analog detector 33xx / 430x (in NORMAL mode) is mounted, the minimum and maximum sensor values can be studied.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.9 2-zone / 2-address dependence (Co- incidence alarm) In some premises 2-zone or 2-address dependent fire alarm ("Two unit dependent" in Win512 version 2.7.x) can be used to avoid unwanted / false alarms (nuisance alarms).
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.9.2 2-address (-unit) dependence Each analog detector, addressable multipurpose I/O unit (3361) monitored Input 0 (Z) and 8 zones expansion board (4580) input, can be programmed for 2-unit dependent fire alarm activation.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.10 Delayed alarm In some premises delayed fire alarm activation can be used to avoid unwanted false alarms (nuisance alarms). The delay time will be added at the end when a fire alarm normally would have been activated in the c.i.e.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.12 Alert Annunciation In some installations the Alert Annunciation function can be used to avoid unwanted false alarms (nuisance alarms) to be sent to the fire brigade.
Page 100
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The AA alarm has to be acknowledged within an acknowledge time and the AA alarm has to be reset within an investigation time, else the output(s) for routing equipment (fire brigade tx) will be activated.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.13 Alarm Acknowledgement Facility (AAF) This facility is used on the Australian market only. The AAF function is similar to the "Alert Annunciation function" (see page 97).
Page 102
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Quiscent state Any detector in alarm? Buzzer ON AP timer starts Detector LED ON AAFC LED ON AAFC button pressed? IP timer starts...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The detectors in an AAF zone can be one to five and not be programmed as 2-unit-dependent and not be controlled by the Alert Annunciation function.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x If the fire alarm routing equipment has provision for transmission of several fire alarm signals and the alarm receiver has provision for reception of several fire alarm signals, a fire alarm type B will indicate that only one detector is activated, which could be a nuisance alarm.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Disabled alarm points and outputs are indicated by LED Fault / Disablements "General disablements" on the c.i.e. front and are listed in menu H4/U1-U2.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.18 Disable outputs for routing equipment Disabled and Re-enabled via menu H2/B9. For more information see EBL512 G3 United version 2.7.x Operating Instructions MEW01473.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.22 Test alarm devices The programmable outputs of type "Alarm device" can be collectively activated via menu H8/S5, which make it possible to test the alarm devices.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Conventional smoke detector: The sensitivity will normally increase in most environments. This can result in unwanted false alarms (nuisance alarms) since all conventional smoke detectors (except 4350, see page 124) have a fixed fire alarm level.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.27.1 Creating the alarm texts via Win512 version 2.7.x In the dialog box for any alarm point (e.g. a detector/sensor), there is a "Text" field where the alarm text for that alarm point can be typed (or edited).
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Text column Shows already programmed alarm texts. Texts can be typed / edited here. NOTE! If any alarm point shall have a different alarm text in one or more of the "display units"...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 16.28.1 Daylight saving time The time is automatically changed when the Daylight saving time period starts and stops respectively, if set so in Win512 version 2.7.x.
Zone-Address" list. Download: (When connected and logged on to an EBL512 unit.) For download of SSD to one or more EBL512 and EBL512 G3 units in a mixed system. Backup: (When connected and logged on to an EBL512 unit.) For backup (upload) of SSD from all the EBL512 units.
Page 113
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Settings: Some settings (e.g. for communication), convention, etc. Download software: (When connected and not logged on to an EBL512.) For download of S/W (+ S/W text file) to the EBL512 unit.
(cut-off) or single short circuit in the TLON network. EBL512 G3 units with the S/W EBL512 G3 United version 2.7.x makes it possible to use EBL512 G3 units (5000 / 5001) together with EBL512 units (1548 / 1549 / 1550), in a TLON Network, i.e. a mixed system.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x G3 unit). Each one of the other control units in the system is called a "Slave". The master has to be equipped with one or more 8 zones expansion board 1580.
Page 116
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The output for fire alarm routing equipment (fire brigade tx) in the master will be activated as follows: Fire alarm in the system.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x b = master 1580 board no. (0-5). xx = master control unit no. (00-29). 17.2 Several control units TLON Master Fire brigade tx output and routing equipm.
Page 118
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Fire brigade tx Fire brigade tx output output control unit control unit 560/2W 560/2W To one 1580 input in the master Figure 28. The output for fire alarm routing equipment (fire brigade tx) in several control units (slaves) connected in parallel.
Page 119
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x system. (In this case also a fault will be generated, see below.) The input in the master will be "blocked" as follows: ...
18.1.1 Silence alarm devices (inside switch) On the c.i.e. front, the button "Silence alarm devices" (see EBL512 G3 United version 2.7.x Operating Instructions MEW01473, button "P2") is called the "inside switch" and toggles between two states: Alarm devices disabled All programmable outputs of type "Alarm devices"...
Page 121
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The outside switch is turned OFF (i.e. from activated to not activated state). "FAULT: Silence switch active " will be Serviced.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Output for routing equipment (Fire brigade tx) not activated. 18.2 Battery faults For other conventions, see chapter "Security functions", page 153.
Page 123
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 1234567890123456789012345678901234567890 First alarm: 002-03 Alarm number 1 (of 1) ACKNOWLEDGED alarm 002-03 SMOKE User definable alarm text. Menu Only the alarm currently shown in the display will be acknowledged, i.e.
NOTE! NOTE! NOTE! NOTE! NOTE! NOTE! NOTE! The analog detectors 4301 and 4300 can via the address setting tool 3314 be set in different modes. In EBL512 G3 can NORMAL mode be used for both types but the 2312 mode only for 4301. See chapters "COM loop units", page 37 and "Functions / Services / Features",...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Pulse up – down counter 19.1 The detector have a "pulse up – down counter", starting at "0" and cannot be negative.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x activated. 4301: Fire judgement is depending on other alarm and filtering algorithms (see chapter "Functions / Services / Features", page 84). 4300: Fire judgement is depending on other alarm and filtering algorithms (see chapter "Functions / Services / Features", page 84).
Page 127
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Cooking condition, depending on the occurrence of smoke together with rise of temperature, i.e. level 3 = 2S+deltaT > 10. NOTE! S has to be > 2.5 and deltaT has to be > 3.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 19.4.1.4 Clean condition, level 1, 2 & 3 For this learning condition to be adapted there must be no check-mark for level 1, level 2 and level 3 respectively during the learning period, i.e.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x data1 = The average smoke obscuration value (S) for 60 seconds before the alarm threshold level was passed. data2 = The sum of the difference between the smoke obscuration value (S) and the alarm threshold level every second for nine seconds after the counter shows "9".
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x filtering algorithms (see chapter "Functions / Services / Features", page 84). 19.8 Self diagnosis of internal devices The detectors perform an internal check of some vital functions and components (e.g.
EBL512 type 1548 / 1549 / 1550: (Default) Used for an EBL512 version 2.7.x control unit. EBL512 G3 type 5000: Used for an EBL512 G3 United version 2.7.x control unit type 5000. EBL512 G3 type 5001: Used for an EBL512 G3 United version...
Configured number of addresses: 128, 256 or 512. Shall be set to the same as the control unit is configured for. NOTE! In a mixed system (see chapter "Mixed system, page 14) the EBL512 G3 control unit is configured for max. number of addresses, instead of max.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 20.1.5 Selective alarm presentation In a system (i.e. two or more control units in a TLON network) it is possible to choose which control units' fire alarms that shall be presented in the control unit respectively.
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 20.2 Log events Not valid for EBL512 G3 since all events always will be logged in three different type of logs. The general event log can be shown / printed out via menu H4/U6.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x System properties (settings) Figure 30. Win512 version 2.7.x "System" dialog box. NOTE! Default settings in Win512 version 2.7.x are shown but might vary depending on convention.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Multiple reset (default): All activated fire alarms in the system will be reset simultaneously by pressing the "Reset" button. Single reset: One activated fire alarm in the system, shown in the control unit's alphanumeric display on the first row to the left, will be reset by pressing the "Reset"...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Checkbox not marked = Reset of fan control system is global, i.e. all fan control systems in the system will be reset. (Fan control, see page 33.)
21.4 Door open 21.4.1 Indication door open affected by Not valid for EBL512 G3 United version 2.7.x control units. The "Open door" symbol shown in the display is always indicating "any door open in the system". 21.4.2 Disablement of routing equipment ...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Disable by door in any control unit or any external FBP: Door open in any C.U. or any ext. FBP will disable the outputs for routing equipment (Fire brigade and fault tx) in all C.U:s.
Page 140
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 2300 2210 2304 2210 (ION) (ION2) (OPT) (OPT2) Offset, Pre-warning Offset, Fire alarm Offset, Heavy smoke Sampling interval NOTE! If any of these values are changed it might be a violation to the EN54-2 standard.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 21.6.3 Smoke detectors' (3304, 4301, 3316 and 4300) properties Detector: 3304 / 4301(OPT) 3316 / 4300 SMOKE (AMD), i.e. the smoke detector part when decision algorithm is not selected.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x NOTE! If any of these values are changed, it might fasten or delay the alarm activation. 21.7 System information In this tab you can read the following information:...
Page 143
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x version 2.7.x before they can be programmed to a two-zone dependence group. NOTE! Only conventional zones (i.e. zone lines with conventional detectors) should be used in the two-zone dependence function.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Compatibility Regarding backwards compatibility: Addressable short circuit isolator 4370 is compatible with Addressable short circuit isolator 4313. NOTE! In system EBL512 G3 United version 2.7.x shall all...
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Cable types A fire alarm installation is a safety installation and it is important that the cables used are of correct types and according to national regulations, e.g.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 23.5 Alarm device cables Alarm devices (sounders, etc.), see dwg. 512 G3 – 23, – 35 and – 38. ELQRB 2 x 0.6 mm (0.3 mm ) or equivalent.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x COM loop cable length The cable length and max. COM loop current, are depending on the number and type of loop units and the cable type, see Figure 32 and Figure 33, page 146 and 147 respectively.
Page 148
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Maximum conductor resistance 2 x 1 mm (0.75 mm 24.5 ohm / km Total COM loop unit current consumption Figure 32. Graphs showing the total conductor resistance in relation to the COM loop units' total current consumption.
Page 149
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Maximum cable length Meter 2 x 1 mm (0.75 mm 24.5 ohm / km Total COM loop unit current consumption Figure 33. Graphs showing the cable length in relation to the COM loop units' total current consumption.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Current consumption The different loop units have different current consumption. Note that some units have much higher current consumption in "active state".
Page 151
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Analog smoke detector 2300/2304 + analog base 2312 1.7 / 1.8 3.7 / 3.8 Analog smoke detector 3304 + analog base 3312...
Page 152
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Other units Normal state Alarm state (quiescent) (mA) (activated) (mA) Routing equipment (Fire brigade tx / Fault tx) Acc. to the producer Acc.
Page 153
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x The following table is a help when calculating the cable length and/or the number of units. The table is based on the current consumption at the lowest power supply voltage allowed i.e.
Fuses F, F1 & F2: T6.3A H 250 V (5x20 mm Ceramic). Batteries inside the c.i.e.: Max. 28 Ah. EBL512 G3 is a very flexible system, i.e. number of and types of loop units, number of and types of expansion boards, ext. FBPs, ext.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 26.1 Charger functions According to EN54-4, section 5.3.1 b): The charger shall be designed and rated so that a battery discharged to its final voltage can be recharged to at least 80% of its rated capacity within 24 hours and to its rated capacity within another 48 hours.
I = current consumption for all other equipment alarm state. The total EBL512 G3 current consumption in Normal ( quiescent ) state: I The total EBL512 G3 current consumption in Alarm ( activated ) state: I Comments regarding (I Including the COM loop units but excl.
< 6.3 A. (The battery charging will be turned off in conjunction with fire alarm activated in the system.) For the total EBL512 G3 current consumption in relation to backup time, see tables in chapter "Battery (second power source)", page 155.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x A battery > (24) 28 Ah has to be placed outside the control unit. NOTE! For external batteries the following is valid: Max. 3 m cable length (min.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x 26.6 Form / Table of current consumption Some national regulations require different forms / tables regarding current consumption, to be filled-in. In such a case an ampere meter shall be used to read a true value instead of a calculated current consumption.
(the date of this document or date of revision). NOTE! The table is valid for an EBL512 G3 control unit connected in a mixed network, i.e. both EBL512 G3 control unit(s) and EBL512 control unit(s) in the same TLON Network.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Technical data Voltage Primary (V AC): 230 (176-264) -- 1.6 A System (V DC): 24 Current consumption (A) Quiescent / active: Depending on type (5000 or 5001), type and number of exp.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Limitations See also "Control Unit / TLON Network", page 18. 29.1 User definable texts At least 617 "User definable texts" can be programmed per c.i.e.
Page 163
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Item C.i.e. System General fire alarm via progr. input External fault via progr. input Programmable outputs (= control expressions) Addressable 2 voltage outputs unit...
National regulations When planning a fire alarm installation, national regulations, customer demands, etc. have to be followed. EBL512 G3 United version 2.7.x is very flexible. Many functions / facilities are built-in the system, e.g. in the S/W and Win512 version 2.7.x.
Panasonic Eco Solutions Nordic AB MEW01472 Rev: - Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x Drawings / connection diagrams Resulting from continual development and improvement, all dimensions quoted are approximate only and subject to change without notice, as are other technical features and data.