Panasonic Aquarea PAW-HPM1 Installation And Commissioning Manual page 18

Heat pump manager (hpm)
Table of Contents

Advertisement

Easy Setup Overview
7
3
18
Step 7
Perform settings for "Heating circuit"¹
Name
7-1
Room com-
pensation
if 7-1 room compensation = 1 (room thermostat installed):
7-1.1 system
if 7-1 room compensation = 2 (room thermostat installed):
7-1.2 room
if 7-1 room compensation = 2 (SP potentiometer installed):
7-1.3 SPPoti
7-2
hCu-slope
7-3
hCu-exp
7-4
roomOT1
7-5
roomOT2
7-6
roomNO
7-7
maxFl
1 All settings for the "Heating circuit" must also be performed for heating circuit 2 (if available).
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Information text
0: no; 1: Thermostat; 2: Ed-
Sensor/SP-poti
System main switch
Room temperature
Setpoint potentiometer
Characteristic curve gradient
Heating element exponent
Setpoint OT1
Setpoint OT2
Setpoint NO
max. flow temp.
Standard
Remark
setpoint
0
0
Assign terminal: terminal 25 or 26
110
Assign available input terminal
(17 - 24) e.g. terminal 24;
110: sensor for ext. display (PAW-
HPMED)
0
Assign available input terminal
(17 - 24) e.g. terminal 23;
0.5
Slope of heating characteristic;
0.5: Floor heating at –15 °C outside
temp., about 35 °C flow temp.
0.7: Low temperature heating
element at –15 °C AT, about 45 °C
flow temp.
1.0: Standard heating element at
–15 °C AT, about55 °C flow temp.
1.3: Standard heating element at
–15 °C AT, about 65 °C flow temp.
1.30
1.10: Floor heating (up to 35 °C)
1.20: Low temperature heating
element (up to 45 °C)
1.20 to 1.40: Radiators and pan-
el-type radiator (up to 55 °C)
1.40 to 1.66: Convectors (up to
65 °C)
22.0 °C
Room temperature, which can be
achieved according to the heating
characteristic
22.0 °C
Is only shown during activated timer
function
15 °C
65.0 °C
(Continue on next page)