Panasonic Aquarea PAW-HPM1 Installation And Commissioning Manual page 75

Heat pump manager (hpm)
Table of Contents

Advertisement

Domestic hot water
Name
Information text
Domestic hot
water
SP-OT1
Setpoint OT1
SP-OT2
Setpoint OT2
SP-NO
Setpoint NO
maxSP
max. setpoint tank temperature °C
maxDemFl-T
max. flow temp. requirement
thermDes
Therm. Disinfection
SP-DHWta
Tank setpoint Therm.
Disinfection
SP-loadFl
Loading flow setpoint therm.
disinfection
day
0: daily 1-7: Monday-Sunday
time
Time start thermal disinfection
maxDuration
maximum duration therm.
disinfection
thermDOn
Therm. Disinfection relay
output BoosterH
Domestic hot
further parameter: Solar
water
TDiffSolOn
TDiffSolOff
maxTSolTa
maxTcoll
collFrLim
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Unit
St-SP Min.
Max.
°C
45.0
2.0
160.0 Tank setpoint for occupation time 1
°C
45.0
2.0
160.0 Tank setpoint for occupation time 2
°C
2.0
2.0
160.0 Tank setpoint for non-occupation time
70.0
2.0
160.0 Setpoint limitation of domestic hot water tank
°C
70.0
0.0
160.0 Limit of maximum setpoint that is transferred
0
0
1 Activation of the anti-legionella circuit, the do-
°C
70.0
60.0
160.0 Tank setpoint that must be reached
°C
85.0
60.0
160.0 Setpoint which is passed to the HP during the
1
0
7 Weekday (daily), at which the therm. disinfec-
01:00
00:00
23:59 Time at which the therm. disinfection should
min
240
0
600 Duration within which the tank has to reach the
0
0
255 Assigning a relay output terminal (1-13) via
K
8.0
0.0
30.0 to switch on the solar pump, the solar collector
K
2.0
0.0
20.0 Shutdown occurs when the collector temp. is
°C
70.0
20.0
160.0 Solar pump is locked when set temp in tank is
°C
110.0
70.0
160.0 if the collector exceeds the set temperature,
°C
–10.0
–50.0
10.0 if the collector drops below the set tempera-
Commissioning
Remark
temperature
to the HP
mestic hot water tank is thermally disinfected;
0: no, 1: Automatic
thermal disinfection
tion should be performed
start
setpoint of the therm. disinfection, otherwise
an error message occurs
which the domestic hot water electric heat-
ing element (during therm. disinfection) is
switched on
x, x K must be warmer than the tank
still x, x K warmer than the tank
exceeded
then the solar pump is switched on for heat
dissipation
ture, the solar pump is switched on as frost
protection
8
75