10.2 Measured value table for sensors

The HPM controller is factory set for the use of Pt1000 standard resistor sensors.
To check a sensor, both wires of the measuring line must be separated from the HPM controller.
The temperature-dependent resistance of the sensor can then be measured with a multimeter.
The measured value must correspond to the raw value, which is displayed by the HPM, once
the sensor has been connected again. The raw value is shown in the Configuration » Inputs »
Term.xx sensor menu. To access the Configuration menu, the respective access code must
be entered.
Sensor measured values
Tempera-
ture
(°C)
–28
–26
–24
–22
–20
–18
–16
–14
–12
–10
–8
–6
–4
–2
0
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
Raw value
Tempera-
Raw value
(kOhm)
ture
(kOhm)
(°C)
0.890
2
0.898
4
0.906
6
0.914
8
0.922
10
0.929
12
0.937
14
0.945
16
0.953
18
0.961
20
0.969
22
0.976
24
0.984
26
0.992
28
1.000
30
Tempera-
Raw value
ture
(kOhm)
(°C)
1.008
32
1.125
1.016
34
1.132
1.023
36
1.140
1.031
38
1.148
1.039
40
1.155
1.047
42
1.163
1.055
44
1.171
1.062
46
1.179
1.070
48
1.186
1.078
50
1.194
1.086
52
1.202
1.093
54
1.209
1.101
56
1.217
1.109
58
1.225
1.117
60
1.232
Appendix
Tempera-
Raw value
ture
(kOhm)
(°C)
62
1.240
64
1.248
66
1.255
68
1.263
70
1.271
72
1.278
74
1.286
76
1.294
78
1.301
80
1.309
82
1.317
84
1.324
86
1.332
88
1.340
90
1.347