The Settings sub-menu comprises the most important parametesr for the heat pump. The basic
settings are shown in the following table.
Some parameters were already automatically set by the selected system diagram (e.g. if a
domestic hot water tank is available or not, Tank = 0 or 1).
Name
Thermost
Tank
BoosterH
AntiFr
BoostDel
HeaterC
Cooling
pumpRotRate
DeviceHeat
BackupH-T
After adjusting the parameters, the supply voltage of the heat pump must be switched off to
establish the connection between the controller and heat pump using the adapter cable PAW-
HPMINT-x (appropriate to the heat pump type) The adapter cable is plugged in on the side of
the heat pumps in the respective circuit board plug for the control panel cable (→ Connections
of the Heat Pumps, P. 58).
The other end of the adapter cable is connected to the BUS interface of the HPM controller
(→ Connection to the HPM controller during communication, P. 64). Upon successful
connection, a beep will sound on the heat pump to confirm.

8.3.2 Heat source - strategy

On system diagrams with more than one heat pump, the demand-driven operation of the heat
pumps are controlled according to the settings in sub-menu Strategy. Via a control change,
the operating times can be evenly distributed over the heat pumps. This achieves a balance of
service life, maintenance intervals and signs of wear between the heat pumps.
Aquarea Heat Pump Manager (HPM) – Manual Part 1: Installation and Commissioning – 12/2014
[▼]
button, select the Function sub-menu and confirm with
[OK]
button.
[▼]
button in the Aquarea menu, select the Settings sub-menu.
[OK]
button.
The parameters in the sub-menu Settings are displayed and can be adjusted
as required.
Information text
external room thermostat
Domestic hot water tank
Domestic hot water E-heating element
Water frost protection function
Time delay domestic hot water E-heating
element
Output e-add heating interior unit
Cooling mode
Pump rotation speed
Add.DH
Backup heater to support heating up the
sanitary water tank
[▼]
button, select the area Aquarea
Settings
0: no 1: yes
0: no 1: yes
0: no 1: yes
0: no 1: yes
Range: 20...95 min, Standard setpoint: 60 min
Range: 1, 2, 3, 6, 9 kW, Standard setpoint: 3 kW
0: no 1: yes
Range: 0...7,
Standard setpoint: 4
0: no 1: yes
0: no, 1: de-icing,
2: outside < 5°C
0: no, 1: yes;
Standard setpoint: 0
Commissioning
[OK]
.
starting from
generation "F"
starting from
generation "F"
starting from
generation "F"
on All in One split heat
pump models