Analyzing Self-Test Results - Simplex 4100ES Operator's Manual

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

TrueAlert ES Appliance Self-Test ,
Analyzing Self-Test
Results
Category
Passed
Failed
Unsupported
*Troubles will only be triggered if the "Trouble on Fault" option is set to "Yes".
___________________________________________________________________________
Once the Self-Test is complete, the panel will display the test results and group the
devices into different categories.
Consult Table 8-4 for the explanation of the various diagnostics:
Diagnostic
The test results indicate that the
Normal
appliance component is functioning
properly.
The audible or visual sensor did not
No Output
detect any sound or light from the
appliance.
-The appliance did not return a result
before the test ended.
-The test was deactivated for a tested
component. For example, if the "Volume"
No Result /
option is set to "Silent", all audible (horn
Not Tested
or speaker) components will display this
result.
The appliance tested is a legacy
notification appliance and is not
Unsupported
compatible with the TrueAlert ES Self-
Test.
_______________________________________________________________________________
Continued
Table 8–4. View Results Options
Definition
User Action
N/A
To clear the trouble* the
appliance must be repaired
and re-tested. A panel
hardware reset will reset
the pseudo but will not
automatically clear the
trouble.
This trouble* can be cleared
by performing a panel
hardware reset.