Simplex 4100ES Operator's Manual page 28

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

Acknowledging Troubles,
Individually
Acknowledging
Troubles
Continued
2.
Press the Trouble Ack key. Repeat this step and read the reports. You need to do this for
each trouble event. The following occurs
The tone-alert silences and the LED glows steady
The alphanumeric display shows the area and type of problem, as shown below.
FIRST FLOOR EAST WING
FIRE MONITOR ZONE OPEN CIRCUIT TROUBLE
3.
Read the alphanumeric display. Investigate the trouble to determine its cause. Restore or
replace defective device (switch, wire, notification appliance, etc.) in accordance with the
manufacturer's instructions.
When the trouble clears, the Trouble LED flashes and the tone-alert sounds steady.
4.
Press the Trouble Ack key. The display shows the system status. Press the Trouble Ack
key again. After a delay, the display shows that the system status is normal.
Press ACK key to acknowledge
ROOM31
18