1 5 B T Esting Each Truealert Power Supply's Slc - Simplex 4100ES Operator's Manual

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

TrueNAC Voltage Drop Test,
T esting all TrueAlert
1 1 4 B
Power Supply's
SLCs
T esting each
1 1 5 B
TrueAlert Power
Supply's SLC
Continued
3. Press the <ENTER> key on the Display/Action keypad. If the test is successful, the following
message displays.
ALL TPS SLCs
TrueAlert TEST COMPLETED
_______________________________________________________________________________
Use the following procedure to test separately each of the TrueAlert Power Supply's SLC lines.
Before you start this test, make sure you have already completed the procedure Accessing the
TrueNAC Voltage Drop Test.
1. Press the <NEXT> key on the Display/Action keypad. The following message displays.
CARD X, TRUEALERT POWER SUPPLY
<ENTER>=Select Channel
2. Press the <ENTER> key on the Display/Action keypad. The following message displays.
TPS CARD: X Channel: X
<ENTER>=Enable TrueNAC Test
3. Use the <NEXT> and <PREVIOUS> keys on the Display/Action keypad to change the SLC
channel.
4. Press the <ENTER> key on the Display/Action keypad. The following message displays.
TPS CARD: X Channel: X
<ENTER>=HORN ON
5. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the
<NEXT> and <PREVIOUS> keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two passes one
with horns on and one with horns off. This is done to enhance measurement accuracy with A/V's.
_______________________________________________________________________________
Continued on next page