TrueNAC Voltage Drop Test,
A ccessing the
1 1 2 B
TrueNAC Voltage
Drop Test
T esting all TrueAlert
1 1 3 B
Power Supply's
SLCs
Continued
_______________________________________________________________________________
2. Press the <NEXT> key on the Display/Action keypad. Use the <NEXT> and <PREVIOUS>
keys to scroll to the Diagnostic Functions. The following message displays.
Press <NEXT> or <PREVIOUS> to scroll
Diagnostic Functions?
3.
Press the <ENTER> key on the Display/Action keypad. Scroll to the TrueNAC Voltage Drop
Test using the <NEXT> and <PREVIOUS> keys on the Display/Action keypad. The
following message displays.
Press <NEXT> or <PREVIOUS> to scroll
TrueAlert TrueNAC Test?
4. Press the <ENTER> key on the Display/Action keypad. The following message displays.
ALL TPS SLCs
<ENTER>=Enable TrueNAC Test
_______________________________________________________________________________
Use the following procedure to test all the TrueAlert Power Supply's SLC lines at once. Before
you start this test, make sure you have already completed the procedure Accessing the TrueNac
Voltage Drop Test.
1. Press the <ENTER> key on the Display/Action keypad. The following message displays.
ALL TPS SLCs
<ENTER>=HORN ON
2. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the
<NEXT> and <PREVIOUS> keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two passes one
with horns on and one with horns off. This is done to enhance measurement accuracy with A/V's.
_______________________________________________________________________________
Continued on next page
52