Simplex 4100ES Operator's Manual page 34

Fire alarm system
Hide thumbs Also See for 4100ES:
Table of Contents

Advertisement

Acknowledging Supervisory Conditions,
Individually
Acknowledging
Supervisory
Conditions
2.
Press the SUPV ACK key. Repeat this step and read the reports. The alphanumeric display
shows the area and type of condition. The tone-alert silences and the yellow LED glows
steady.
a.
The tone-alert silences and the LED glows steady.
b.
The display shows the area and type of problem, as shown below.
FIRST FLOOR EAST WING
Press <ACK> key to acknowledge
FIRST FLOOR EAST WING
FIRE PUMP MONITOR
3.
Read the alphanumeric display. Investigate the problem to determine its cause. Restore or
replace the defective device (switch, wire, notification appliance) in accordance with the
manufacturer's instructions, or call Simplex to repair the system.
When the problem causing the condition is corrected, the SUPERVISORY LED flashes and
the tone-alert sounds steady.
4.
Press the SUPV ACK key. The display shows the system status.
5.
Press the SUPV ACK key again. After a short delay, the display indicates that the system is
normal.
Continued
ROOM 31
OR
ROOM 31
RUNNING
24