7 Checkout procedure

When the installation is complete, verify that the remote Annunciator is working correctly:
1.
Execute a lamp test to verify that the LEDs and the LCDs are working, see
2.
Verify that the Annunciator communicates correctly with the FACU by observing the remote Annunciator. The Annunciator displays
error messages and emits an audible signal if it is not wired correctly and is not communicating with the FACU. The FACU also displays
a card communication failure trouble.
Note: For Programming changes, refer to the relevant FACU programming manual.
7.1

Executing the lamp test

To execute the lamp test, complete the following steps:
1.
Insert the key into the keyswitch.
2.
Turn the key anticlockwise until it is in the unlock position, see Figure 13.
3.
Press and hold the RESET key for at least 10 seconds to execute the lamp test.
page 19
Foundation Series 2606-9101 LCD Annunciator Installation Guide
Executing the lamp
test.