Chapter 2
Installation/Wiring

Standard Adapter Board

LANGUAGE
MODULE
À À À À À À
À À À À À À
D1
J10
1
D2
20
TE
1
Jumper
+5V DC
J13
1 to 2
2–28
When installing and wiring the Standard Adapter board, you need to deal
with the following issues:
Control and Signal Wiring
Interface Board Installation and Removal
Control & Signal Wiring – If your 1336 FORCE Drive is equipped with
a Standard Adapter Board, terminal blocks TB5, TB6 and TB7 located at
the bottom center of the board (Figure 2.15) are used for control and signal
wiring (Drive Permissives). The Standard Adapter Board is connected to
the Main Control Board through J1, the Main Control Interface.
The maximum and minimum wire size accepted by TB5, TB6 and TB7 is
3.3 and 0.06 mm
blocks is 0.79 N–m (7 lb. – in.). Recommended control signal wire is:
Belden 8760 or equiv. – 0.750 mm
Belden 8770 or equiv. – 0.750 mm
Belden 9460 or equiv. – 0.750 mm
Figure 2.15.

Standard Adapter Board Connections

J1
Main Control
Interface
J5
BRAM
EN
DIS
L OPTION BOARD
J13
1
3
TB5
14
1
+12V DC
Purpose
2 to 3
Pulse Input Voltage Selection
2
(12 and 30 AWG). Maximum torque for these terminal
2
(18 AWG), Twisted Pair, Shielded
2
(18 AWG), 3 – Conductor, Shielded
2
(18 AWG), Twisted Pair, Shielded
LED
TP1
+5V
D1 (Green)
TP2
DGND
TP3
+15V
TP5
AGND
D2 (RED)
TP6
–15V
TB6
8
1
Jumper
J5
STATE
DESCRIPTION
OFF
D2 On or No Power
Flashing
Adapter Warning Fault
Solid ON
Adapter OK
OFF
D1 On or No Power
Flashing
Adapter Soft Fault
Solid ON
Adapter Hard Fault
Refer to Fault Codes in Table 6.B
TP7
TP8
ISO COM
12V ISO
Port 1
J12
J11
20
Port 2
J9
1
TE
TB7
12
Purpose
Position
1 to 2
BRAM Write Enable
2 to 3
BRAM Write Disabled

Hide quick links: