10 Volt Input
[10 Volt Input]
This parameter displays the converted
analog value of the +/– 10 volt input.
10 Volt Offset
[10 Volt Offset]
This parameter determines the offset ap-
plied to the raw analog value of the +/– 10
volt input before the scale factor is applied.
This allows the user to shift the range of
the analog input.
10 Volt Scale
[10 Volt Scale]
This parameter determines the scale factor
or gain for the +/– 10 volt input. The +/– 10
volt input is converted to +/– 2048 and
then the scale is applied which allows an
effective digital range of +/– 32767.
Pot Input
[Pot Input]
This parameter displays the converted
analog value of the pot input.
Pot Offset
[Pot Offset]
This parameter determines the offset
applied to the raw analog value of the pot
input before the scale factor is applied.
This allows the user to shift the range of
the of the analog input.
Pot Scale
[Pot Scale]
This parameter determines the scale factor
or gain for the pot input. The pot input is
converted to a +/– 2048 and then the scale
is applied allowing an effective digital range
of +/– 32767
Milli Amp Input
[mA Input]
This parameter displays the converted
analog value of the milli amp input.
Parameter Number
355
Parameter Type
Source
Display Units
+/– x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
Parameter Number
356
Parameter Type
Sink
Display Units
+/– x.xx volt
Drive Units
205 = 1 volt
Factory Default
+0.00 volt
Minimum Value
–20.00 volt
Maximum Value
+20.00 volt
Parameter Number
Parameter Type
Display Units
Drive Units
Factory Default
Minimum Value
Maximum Value
Parameter Number
Parameter Type
Display Units
Drive Units
Factory Default
Minimum Value
Maximum Value
Parameter Number
Parameter Type
Display Units
Drive Units
Factory Default
Minimum Value
Maximum Value
Parameter Number
Parameter Type
Display Units
Drive Units
Factory Default
Minimum Value
Maximum Value
Parameter Number
Parameter Type
Display Units
Drive Units
Factory Default
Minimum Value
Maximum Value
Chapter 5
Programming Parameters
357
Sink
+/– x.xxx
2048 = 1
+2.000
–16.000
+16.000
358
Source
+/– x
None
0
–32767
+32767
359
Sink
+/– x.xx volts
205 = 1 volt
+0.000 volt
–20.000 volt
+20.000 volt
360
Sink
+/– x.xxx
2048 = 1
+1.000
–16.000
+16.000
361
Source
x
None
+0
0
+32767